9.3 Fault indications on the power supply

10.0 Dismantling the valve and the housing

Green
"DC OK"
LED

Meaning

Description

Corrective measure

Lit

Output voltage > 27 V Output voltage and current OK

The power supply is functioning
correctly

Blinking

Output voltage < 27 V Power supply in operation but

- Fault at load
- Current consumption > IBOOST
- Output short-circuited

- Disconnect and exchange the

defective load

- Reduce the current consumption,

either by connecting an
additional power supply or by
disconnecting any loads that are
not required

- Remove the short-circuit

Off

No voltage at output

Power supply not in operation
because
- No mains voltage present
- Primary fuse has tripped
- Device is defective

ATTENTION !
Check the following points carefully:
- The piping system must be pressureless.
- The medium must be cool.
- The plant must be drained.