4.3 Indications on the CONA

®

-control system

The LEDs on the "central status indication" light up continuously to indicate the existence of
a fault. As soon as the steam trap functions correctly again, the LEDs blink to show that the
faults are no longer present. By pressing the Reset button, you can reset a stored fault.

* If the "central status indication" is used, the fault is stored and the "Trap Inspect" LED
blinks.

Sectional view of

test chamber and steam trap

LED on measuring

amplifier -

indication via bus

Operating status

Fig. 1

Trap Inspect *

Blockage
Steam

Leakage

Plant / steam trap

not in operation

Sensor surrounded by

cold

air / steam and

temperature is below

specified value

Fig. 2

Trap Inspect *

Blockage
Steam

Leakage

Steam trap is working

correctly

Sensor surrounded by

hot condensate

Fig. 3

Trap Inspect *

Blockage
Steam

Leakage

Steam leakage

Sensor surrounded by

steam and temperature is

above specified value

Fig. 4

Trap Inspect *

Blockage
Steam

Leakage

Blocked steam trap

Sensor surrounded by

cold condensate and / or

condensate temperature

is below

specified value