3 operating instructions, 1 restart after a power failure, 3 operating instructions -31 – ARI Armaturen CONA control EN User Manual

Page 31: 1 restart after a power failure -31, Operating and installation instructions cona, Control 6.3 operating instructions

Advertising
background image

Rev. 0040807014 1614

Page 2-31

Operating and Installation Instructions

CONA

®

-control

6.3 Operating instructions

Various faults may be indicated when the plant is shut down (see 6.3.2 Shutting down the
plant
). These fault
s must be reset when the plant is started up again.

Through film condensation at the sensors, instantaneous steam leakages will be
announced lately. First the body temperature must be conditioned to the steam temperature
(ca. 10 -15 min.).
The same problem appears at high condensate sub-cooling.

6.3.1 Restart after a power failure
The bus system restarts automatically after a power failure.
The PLC program also starts automatically.
All faults that were stored before the power failure are lost!

28

Slave 24B

Slave 25B

-

-

LED-

Steam

Leakage

LED-

Blockage

-

-

LED-

Steam

Leakage

LED-

Blockage

29

Slave 26B

Slave 27B

-

-

LED-

Steam

Leakage

LED-

Blockage

-

-

LED-

Steam

Leakage

LED-

Blockage

30

Slave 28B

Slave 29B

-

-

LED-

Steam

Leakage

LED-

Blockage

-

-

LED-

Steam

Leakage

LED-

Blockage

31

Slave 30B

Slave 31B

-

-

LED-

Steam

Leakage

LED-

Blockage

Not

assigned

Not

assigned

Not

assigned

Not

assigned

NOTE !
All faults that are stored when the plant or part of the plant is shut down must be
reset on the central status indication whenever the CONA

®

-control test system or

the plant is started up.
- To reset all stored faults, press any RESET button on the central status

indication for at least two seconds.

- To reset a single stored fault, press the appropriate RESET button for less than

two seconds.