0 putting the system into operation, 0 putting the system into operation -23 – ARI Armaturen CONA control EN User Manual

Page 23

Advertising
background image

Rev. 0040807014 1614

Page 2-23

Operating and Installation Instructions

CONA

®

-control

6.0 Putting the system into operation

6.1 Measuring amplifiers without a central status indication

The mains voltage can be switched on after all work has been completed.
The measuring amplifier or amplifiers are now ready for operation.

ATTENTION !
- The central status indication and the measuring amplifiers are only allowed to

be operated without the hood / cover in case of essential adjustment work.
Some non-insulated parts of the central status indication are live (dangerous
voltage!) while this work is taking place.

- Incorrect or careless performance of the adjustment work can result in death,

severe personal injury or substantial property damage.

- Operation of the central status indication or the measuring amplifier without the

hood / cover is prohibited for all purposes other than that described above.

- The electronics must be free from moisture.
- All local safety instructions must be observed.
Before putting a new plant into operation or restarting a plant after repair or
modification, always make sure that:
- The power supply and ambient temperature coincide with the technical data of

the electronics.

- All work has been completed correctly.
- The hood of the central status indication and the covers of the measuring

amplifiers are mounted again following the completion of the adjustment work.