6.2 Measuring amplifiers with a central status indication

- Switch on the mains voltage

The "prj mode" LED lights up when

configuring mode is active.

Thirty measuring amplifiers and thirty
indication cards are configured / preset in
the factory. If these settings are not
correct, the system indicates a "fault" and
shows the incorrectly configured slaves
(measuring amplifiers and indication
cards) on the AS-i / PROFIBUS gateway.
The type of slave fault is indicated by a
dot.
Proceed as follows to confirm the detected
or installed number of measuring
amplifiers and indication cards
(configuration):

Fig. 19

- Change to configuring mode: There

must not be a bus connection to a higher-
level system. Disconnect the bus
connector (if connected).
Press the "Mode" button for at least five
seconds.
The "prj mode" LED lights up and the
connected slaves are shown in the digital
display for 0.5 seconds.

- Store the AS-i configuration:

To confirm the current configuration:
Press the "Mode" button again for at least
five seconds.
The "fault" indications should then
disappear and the incorrectly configured
slaves should no longer be shown.