2 fault indications on the as-i gateway, 2 fault indications on the as-i gateway -34, Operating and installation instructions cona – ARI Armaturen CONA control EN User Manual

Page 34: Control 9.2 fault indications on the as-i gateway

Advertising
background image

Page 2-34

Rev. 0040807014 1614

Operating and Installation Instructions

CONA

®

-control

9.2 Fault indications on the AS-i gateway

Indication

Meaning / cause

Corrective measure

power

The master is receiving sufficient power

The AS-i master is functioning correctly

Profibus

LED on: the gateway is assigned to a
Profibus master

LED off: The gateway is not assigned to a
PROFIBUS master

fault

If a "fault" is indicated, the number of the
faulty slave and the reason for the fault are
shown by a dot in the digital display

Possible causes of the fault:
- There is an error in the configuration.
- At least one configured slave is not detected

or at least one detected slave is not
configured or the actual configuration data
of at least one configured and detected
slave does not match the preset
configuration.

- A periphery fault has occurred in at least

one
AS-i slave. If both a configuration error and
a periphery fault are detected, only the
configuration error is indicated.

- Check the slave addresses
- Check the configuration and if necessary

store the current configuration (refer to 6.2
Measuring amplifiers with a central status
indication)

- Clear the periphery fault on the slave

U AS-i

The AS-i circuit is receiving sufficient power

The AS-i circuit is functioning correctly

AS-i active

Normal operation (the LED blinks to indicate
B slaves)

Bus communication is active in the AS-i
circuit.

prg enable

Addresses can be programmed automatically If exactly one slave is not detected in the

protected operating mode, it can be replaced
by an identical slave with the address zero.
The master automatically addresses the new
slave at the incorrect address. The
configuration error is thereby corrected

prj mode

The AS-i master is in configuring mode

Press the "Mode" button for at least
5 seconds. The current configuration is
stored and the AS-i master changes to the
protected operating mode