Campbell Scientific SDM-IO16 16-Channel Input/Output Expansion Module User Manual

Page 10

Advertising
background image

SDM-IO16 16 Channel Input/Output Expansion Module

Minimum frequency:

a frequency of 0 Hz is measured if there are
less than two high-to-low signal transitions in
the measurement interval.

Minimum pulse width:

a pulse must stay high or low for a minimum
of 244

μsec for a change of state or pulse to be

counted.

Switch debounce timing:

with the default settings a switch between the
input and G must remain closed for 3.17 msec
and then remain open for 3.17 msec, to be
counted as a closure2. The debounce time can
be changed from the user program.

Accuracy:

internal clock accuracy

±0.01% (worst case)

over the standard temperature range of -25 to
+50

°C. See also Appendix A for a discussion

on frequency resolution.

Duty cycle resolution:

this depends on frequency and measurement
interval - See Appendix A. The average duty
cycle can be measured for signals up to 4 kHz.

Max measurement interval: for frequency or duty cycle measurements the

datalogger must request a measurement at an
interval no longer than 15.9375 seconds. Each
channel can be measured at different intervals,
both for frequency and duty cycle.

1

If more detailed input/output characteristics are required, experienced users

should consult the equivalent circuit diagrams shown in Figure 2.

2

See Appendix A for a more detailed discussion of switch debounce, resolution

and accuracy.

4

Advertising