SDM-IO16 16 Channel Input/Output Expansion Module

TABLE 2. Bit Period Values


Datalogger

Default
Bit Period

Minimum Allowable
Bit Period

Maximum
Bit Period

CR800, CR850 26.04

μsec 8.68

μsec

2.2 msec

CR1000

26.04

μsec 8.68

μsec

2.2 msec

CR3000

26.04

μsec 8.68

μsec

2.2 msec

CR5000

30

μsec 8

μsec

3 msec

The equation used to calculate the bit rate depends on the datalogger used.
The datalogger will round down to the next faster bit rate.

Equation for CR800, CR850, and CR1000:

bit_rate=INT((k*72)/625)*Resolution

Where:
k= the value entered in BitPeriod

Resolution=8.68 microseconds

Equation for CR3000:

bit_rate=INT((k*144)/625)*Resolution

Where:
k= the value entered in BitPeriod
Resolution= 4.34

μsec.

Equation for CR5000:

bit_rate=INT(k*20)*Resolution

Where:
k= the value entered in BitPeriod
Resolution=50 nsec.

6.3 Edlog Programming

Dataloggers that use Edlog include our CR10(X), CR23X, 21X, and CR7.

6.3.1 Instruction 188 (CR10X and CR23X)

Edlog Instruction 188, ‘SDM-IO16’, supports control of the
SDM-IO16. This instruction is included in the latest versions of the operating
systems for the CR10X and CR23X dataloggers. Instruction 188 is specifically
designed to control the SDM-IO16, and takes the following form: