SDM-IO16 16 Channel Input/Output Expansion Module

;Maximum windspeeds with time of maximum
11: Maximum (P73)
1: 4

Reps

2: 10

Value

with

Hr-Min

3: 2

Loc [ Windspd_1 ]


;Totalize the rainfall over the previous hour
12: Totalize (P72)
1: 4

Reps

2: 6

Loc [ Rain_1 ]


*Table 2 Program
02: 0.0000 Execution

Interval

(seconds)


*Table 3 Subroutines

End Program

7.4 A CR10X Program that uses the Interrupt Subroutine in the

Datalogger to Record the Time of Change of any one of
the Ports on an SDM-IO16

This program can also be used with a CR23X datalogger.

;{CR10X}
;An example that shows the use of the IO16 to detect the change
;of state of one of the 16 ports and indicate this to the
;datalogger using the I/O line (which should be connected to C8).
;The datalogger in turn reads the status and captures the
;current port status and writes this with a time stamp to memory
;
*Table 1 Program
01: 5

Execution

Interval

(seconds)


;First configure the IO16 if not already done
;If flag 1 is not set, i.e. the program has just
;been compiled or datalogger powered up.
;This code is needed to set the IO16 to pulse its I/O line
;if any port changes state.
1: If Flag/Port (P91)
1: 21

Do if Flag 1 is Low

2: 30

Then

Do

26