SDM-IO16 16 Channel Input/Output Expansion Module

; Call instruction 188 to set the ports up
2: SDM-IO16 (P188)
1: 00

SDM

Address

2: 90

Command

Code

Option

3: 4444

Ports

16-13

;configure the ports

4: 4444

Ports

12-9

;Set so all ports will cause an interrupt

5: 4444

Ports

8-5

6: 4444

Ports

4-1

7: 1

Return Code Loc [ Errcount ]

;for return code

8: 2

First Loc [ Portstat_]

9: 1.0

Mult

10: 0.0

Offset


;Set flag 1 high to indicate we have run the setup code
3: Do (P86)
1: 11

Set Flag 1 High


4: End (P95) ; of IF block

;Now the rest of the other normal measurements would follow

*Table 2 Program
02: 0.0000 Execution

Interval

(seconds)


*Table 3 Subroutines

;Subroutine 98 will be run when a signal is generated by the I/O line
;from the IO16 connected to C8 on the datalogger.
1: Beginning of Subroutine (P85)
1: 98

Subroutine

98


;First read the port status from the IO16 as quickly as possible
;The speed at which the datalogger can respond to the I/O signal will
;determine the minimum pulse width that you can guarantee to capture
;as a change of state of a port. Typically this will be 10 ms but will
;vary with the datalogger and other activity.
;Reading the port status will cancel further polling
;until the next change of state.

2: SDM-IO16 (P188)
1: 00

SDM

Address

2: 91

Command

Code

Option

;read the port status into one location

3: 0

Ports

16-13

;port settings not used for code 91

4: 0

Ports

12-9

5: 0

Ports

8-5

6: 0

Ports

4-1

7: 1

Return Code Loc [Errcount ]

;for return code

8: 2

First Loc [Portstat ]

9: 1.0

Mult

10: 0.0

Offset

27