Troubleshooting – Blodgett SB-G Series User Manual

Page 22

Advertising
background image

20

OM-G-SB

Troubleshooting

Do not operate the unit if it malfunctions or has damaged or broken parts. Steam boilers are designed to operate smoothly and ef-

ficiently when maintained properly. However, the following is a list of checks to make if there is a problem. Electrical schematics are

provided in this manual, and inside the unit electrical enclosure. IF THE ITEM ON THE LIST IS MARKED WITH (X), THE

WORK SHOULD ONLY BE DONE BY A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE.

SYMPTOM

WHO

WHAT TO CHECK

Boiler does not fill with water.

User

a. Is water supply connected and is water present?

b. Is water pressure low (less than 30 PSI)?

c. Is strainer screen (if used) clogged?

d. Is on/off switch in base cabinet turned on? Is the amber light in

the on/off switch “ON”?

e. Is the manual drain valve open?

Authorized

Service Rep Only

f. Is the Water Level Control Board defective? Check for loose

electrical connections on water fill solenoid. (X)

g. Is the water fill solenoid valve defective? (X)

h. Is the solenoid drain valve open or leaking? Check for loose

electrical connections on solenoid drain valve. (X)

Boiler overfills with water.

User

a. Is the boiler level? Check levelness of unit with a spirit level.

b. Is the water pressure too high? (Greater than 60 PSI?)

Authorized

Service Rep Only

c. Is the Water Level Control Board defective? Check for loose

electrical connections on “hi” water fill solenoid. (X)

d. Is the water fill solenoid valve defective? (X) Check for debris on

valve seat.

e. Is the “hi” water probe sensing level? Clean water level probe

and probe well (located in boiler). (X)

Boiler under fills with water.

User

a. Is the boiler level? Check levelness of unit with a spirit level.

Water enters boiler slowly.

User

a. Is strainer screen (if used) clogged?

b. Is the water pressure too low? (Less than 30 PSI)?

c. Is the water supply line too small?

Authorized

Service Rep Only

d. Is the water fill solenoid defective? (X)

RESET light does not come

on.

Authorized

Service Rep Only

a. Is the Is the Water Level Control Board defective? Check for

loose electrical connections on “mid” water fill solenoid. (X)

b. Is the “mid” water probe sensing level? Clean water level probe

and probe well (located in boiler). (X)

c. Is the indicator light defective? (X)

Pilot burner will not light

(spark ignition).

User

a. Is supply gas valve open?

b. Is gas valve knob in the “ON” position?

c. Is the boiler filled with water? Is the green light in the start switch

“ON”?

Authorized

Service Rep Only

d. Does the pilot flame require adjustment? Screw attachment on

gas valve. (X)

e. Is the gas valve defective? (X)

Pilot burner will not stay lit.

Authorized

Service Rep Only

a. Does the pilot flame require adjustment? Screw attachment on

gas valve. (X)

Advertising