Installation – Blodgett SB-G Series User Manual

Page 9

Advertising
background image

OM-G-SB 7

Installation

2. Electrical Supply Connection

a.

Power is supplied to cavity controls and blower from the boiler base,

and no other electrical connections are required.

b.

The maximum electrical load is 4 AMP. You must provide 115 Volt

Alternating Current, 60 Hz, 1PH, 15 AMP service. Local codes and/or the

National Electrical Code should be followed (ANSI/NFPA-70-1987 - or

latest edition). AN ELECTRICAL GROUND IS REQUIRED.

c.

The electrical schematic is located in the electrical enclosure and in

this manual. In Canada provide electrical service in accordance with the

Canadian Electrical Code, CSA C22.1, Part 1 and/or local codes.

3. Water Supply Connection

a.

This Model features two separate water inlets – one for the steam boiler

(treated water), the other for the spray condenser (untreated water). The

second intake will reduce treatment requirements resulting in significant

savings.

b.

Cold water should be supplied to a 3/8” NPT pipe connection for

untreated water at the rear of the unit. A back siphonage device (check

valve) must be installed, complying with local plumbing codes. The

water pressure should be between 30 and 60 PSI (210 to 410 kPa). A

pressure regulator is required above 60 PSI (410 kPa). A strainer screen

at the connection is also recommended, to trap debris before it can

enter the system.

c.

The condenser spray uses 0.70 to 0.95 gallons of water per minute

(2.6 to 3.6 liters per minute) at 30 to 60 PSI (210 and 410 kPa). The

spray will only operate when a steamer cavity (cooking chamber) is in

operation.

d.

Water supply lines should be sized to provide for maximum water use

(the total of the boiler and condenser spray) as shown in the following

table:

Maximum Water Consumption-gal/hr (L/hr)

Gas boiler only

12.9 (48.8)

Steamer Condenser Spray Only-gal/hr (L/hr)

AT 40 PSI (280 kPa)

47.4 (180)

AT 60 PSI (410 kPa)

57.0 (215)

4. Drain Connection

a.

The drain connection is made at the rear of the unit, using a 1-1/4” NPT

pipe. Do NOT use plastic pipe — the piping must be able to withstand

steam and hot water. Extend the drain piping to a nearby floor drain.

Piping of 1 - 1/4” NPT (or 1 - 1/2” NPT) is acceptable for distances of

six feet or less. If the distance to the drain is further than six feet, use 2”

NPT piping.

b.

Install the drain line with a constant downward pitch. Do not allow any

water traps in the line. A trap can cause pressure to build up inside the

cavity during steaming, which will make the door gasket leak. A vertical

air gap must be maintained between the drain line and the building

drain, unless otherwise specified by local plumbing codes.

WARNING

THE UNIT MUST BE INSTALLED BY

PERSONNEL WHO ARE QUALIFIED TO

WORK WITH ELECTRICITY AND PLUMBING.

IMPROPER INSTALLATION CAN CAUSE

INJURY TO PERSONNEL AND/OR DAMAGE TO

THE EQUIPMENT. THE UNIT MUST BE

INSTALLED IN ACCORDANCE WITH ALL

APPLICABLE CODES.

IMPORTANT

IMPROPER DRAIN CONNECTION

WILL VOID WARRANTY.

Leave an air gap between the hose and the building

drain, and don’t allow water traps in the line.

CAUTION

SHIPPING STRAPS ARE UNDER TENSION.

THEY CAN SNAP BACK VIOLENTLY AND

CAUSE INJURY WHEN CUT.

CAUTION

MAKING ELECTRICAL OR MECHANICAL

CHANGES TO THE UNIT WITHOUT APPROVAL

FROM THE FOOD SERVICE ENGINEERING

DEPARTMENT WILL VOID WARRANTIES.

CAUTION

DO NOT LOCATE THE BOILER CABINET

DIRECTLY OVER A FLOOR DRAIN OR

FLOOR SINK. HUMIDITY OR WATER

WILL DAMAGE ELECTRICAL.

Advertising