Piping checklists, General piping checklist – Goulds Pumps 3171 - IOM User Manual

Page 21

Advertising
background image

Support plate

type

Action

Tank flange

Install the supplied gasket between the two flanges. Make sure that the mating

flange on the tank is level. Use gasket material between the flanges in order to make

minor adjustments.

Figure 4: Layout for a standard support plate with the vapor-proof option

4. Hand tighten the anchor bolts. Check the level and re-shim if necessary.
5. Tighten all anchor bolts in a star pattern in order to avoid distorting the support plate.

Piping checklists

General piping checklist

Precautions

CAUTION:

• Never draw piping into place by using force at the flanged connections of the pump. This can impose

dangerous strains on the unit and cause misalignment between the pump and driver. Pipe strain
adversely affects the operation of the pump, which results in physical injury and damage to the equipment.

• Vary the capacity with the regulating valve in the discharge line. Never throttle the flow from the

suction side. This action can result in decreased performance, unexpected heat generation, and
equipment damage.

Checklist

Check

Explanation/comment

Checked

Check that all piping is supported

independently of, and lined up

naturally with, the pump flange.

This helps to prevent:

• Strain on the pump
• Misalignment between the pump and the drive unit
• Wear on the pump bearings and the coupling
• Wear on the pump bearings, seal, and shafting

Keep the piping as short as

possible.

This helps to minimize friction losses.

Check that only necessary fittings

are used.

This helps to minimize friction losses.

Do not connect the piping to the

pump until:

• The grout for the baseplate

or sub-base becomes hard.

• The hold-down bolts for the

pump and the driver are
tightened.

Make sure that all the piping

joints and fittings are airtight.

This prevents air from entering the piping system or

leaks that occur during operation.

Installation (Continued)

Model 3171 Installation, Operation, and Maintenance Manual

19

Advertising