Start the pump, Pump operation precautions, Start the pump pump operation precautions – Goulds Pumps 3171 - IOM User Manual

Page 35

Advertising
background image

Start the pump

CAUTION:

• Immediately observe the pressure gauges. If discharge pressure is not quickly attained, stop the driver,

reprime, and attempt to restart the pump.

• Observe the pump for vibration levels, bearing temperature, and excessive noise. If normal levels are

exceeded, shut down the pump and resolve the issue.

1. Fully close or partially open the discharge valve, depending on system conditions.
2. Start the driver.
3. Slowly open the discharge valve until the pump reaches the desired flow.
4. Immediately check the pressure gauge to ensure that the pump quickly reaches the correct discharge

pressure.

5. If the pump fails to reach the correct pressure, perform these steps:

a) Stop the driver.
b) Prime the pump again.
c) Restart the driver.

6. Monitor the pump while it is operating:

a) Check the pump for bearing temperature, excessive vibration, and noise.
b) If the pump exceeds normal levels, then shut down the pump immediately and correct the problem.

A pump can exceed normal levels for several reasons. See Troubleshooting for information about
possible solutions to this problem.

7. Repeat steps 5 and 6 until the pump runs properly.
8. After the pump is brought to temperature for the first time, shut the unit down temporarily and re-

adjust the impeller clearance.

Pump operation precautions

General considerations

CAUTION:

• Vary the capacity with the regulating valve in the discharge line. Never throttle the flow from the

suction side since this can result in decreased performance, unexpected heat generation, and
equipment damage.

• Do not overload the driver. Driver overload can result in unexpected heat generation and equipment

damage. The driver can overload in these circumstances:
• The specific gravity of the pumped fluid is greater than expected.
• The pumped fluid exceeds the rated flow rate.

• Make sure to operate the pump at or near the rated conditions. Failure to do so can result in pump

damage from cavitation or recirculation.

Operation at reduced capacity

WARNING:
Never operate any pumping system with a blocked suction and discharge. Operation, even for a brief
period under these conditions, can cause confined pumped fluid to overheat, which results in a violent
explosion. You must take all necessary measures to avoid this condition.

Commissioning, Startup, Operation, and Shutdown (Continued)

Model 3171 Installation, Operation, and Maintenance Manual

33

Advertising