Installation, Operation and Maintenance Instruction

Model ICB


ICB 100-English

page 6

Revision 00

Article No 21999991

Issue 05/2006

monitoring devices are necessary to secure the
function.



2.7.7 Electric switches and control device,
Instrumentation and accessories

Electric switches and control devices,
instrumentation and accessories must
correspond with the valid safety requirements
and regulations for explosion protection.

2.8 Use acc. to Regulations

2.8.1 Speed, Pressure, Temperature

Suitable safety measures must be taken at the
plant to ensure that the speed, pressure and
temperature of the pump and the shaft sealing
do not exceed the limit values given in the data
sheet and / or order confirmation. The given
admission pressures (system pressures) must
also be sufficiently high.

Further, pressure shocks, as can occur on too fast
shut down of the facility, must be kept away from the
pump (e.g. by non-return valve at pressure side,
airtanks). Quick temperature changes must be
avoided. They could cause a temperature shock and
lead to damage or impair the function of single
components.

2.8.2 Permitted Nozzle Loads and Torques

Basically the suction and discharge piping must
be designed in such way, that as little forces as
possible are effective to the pump. If that is not
possible, the values shown in chapter 3.5 must
not be exceeded under any circumstances.
This is valid for the operation as well as for the
standstill of the pump and therefore for all
possible pressures and temperatures of the
unit.


2.8.3 NPSH

The pumped liquid must have a min. pressure
NPSH at the impeller inlet, so that cavitation
free work is secured resp. a "break off" of the
pump flow is prevented. This condition is
fulfilled, when NPSH-value of the system
(NPSHA) lies above NPSH-value of the pump
(NPSHR) under all operating conditions.

Attentention must especially be piad to the NPSH-
value on pumping liquids near the vapour pressure. If
the NPSH-value of the pump remains under, this can
lead from damage of the material due to cavitation to
destruction by overheating.
The NPSH-value of the pump (NPSHR) is shown in
the curves of every pump type.

2.8.4 Sealing, Flushing, Cooling
Suitable provisions for the regulation and monitoring
of sealing, flushing or cooling are to be provided.
When handling dangerous liquids or if temperatures
are high, care should be taken to ensure that the
pump ceases operating if the sealing, flushing or
cooling system fails.
Sealing, flushing and cooling systems must always be
operational before the pump is started up. They
should not be taken out of operation until the pump
has stopped, provided that the nature of the operation
allows this at all.

2.8.5 Back Flow
In systems where pumps are operating in closed
circuits under pressure (gas cushions, steam
pressure), the pressure of the gas cushion must not
be reduced via the pump, since the back flow speed
may be much higher than the operating speed, which
would destroy the unit.

3. Description

3.1 Design

ICB-pumps are single-stage volute casing pumps in
block design. Hydraulic design and dimensions
comply with ISO 2858/ EN 22858, the technical
design complies with ISO 5199/EN 25199.
The motors comply with DIN 42677-IM B5. Motor and
pump shaft are coupled rigidly.
The permitted application conditions and design
details of the delivered pump are shown in the
attached data sheet and / or the order confirmation
(see Design Coding System in chapter 3.2).

Installation position: ICB-pump are intended for use
with horizontal shaft, discharge up. Installation
positions deviating therefrom must be approved by
the manufacturer.

3.1.1 Design Coding System

Due to the coding on data sheet and / or order
confirmation all information regarding der delivered
pump can be found in this Installation, Operation and
Maintenance Instruction, e.g.:
ICB 100 - 65 - 250 S1 V L 2 - 132
(0) (1) (2) (3) (4)

(5) (6) (7) (8)

Position (0) - Name of Model

ICB - ISO block pump

Position (1) - Suction Nozzle in mm

Position (2) - Discharge Nozzle in mm

Position (3) - Nominal diameter of impeller in mm

Position (4) - Shaft sealing