Sunlight Supply Grozone Control SCC1 Temperature, Humidity and CO2 Controller Simple One Series User Manual

Page 7

Advertising
background image

7 of 12

Grozone SCC1 Advanced User Guide – March 2012

www.grozonecontrol.com

6- FACTORY SETTINGS AND ALTERNATE SETTINGS

When shipped from the factory, the SCC1 is set with factory settings. These settings are those that a vast majority
of users will be using during their growing experiences. Advanced users may need to change some settings in order
to fix control problems or to improve control performances in some specific set-ups.

Review below the settings that can be changed by the users.
To make these changes, refer to section below: ACCESSING THE

FACTORY / ALTERNATE SETTING

EDIT MODE.

The settings that can be changed are:

1- the CO2 ELEVATION
2- the Fan Output Control DIFFERENTIAL
3- the Humidity Output Control DIFFERENTIAL
4- the CO2 Output Control DIFFERENTIAL
5- the Aux Heater Output Control DIFFERENTIAL
6- the LOW TEMPERATURE LIMIT
7- the HIGH TEMPERATURE LIMIT
8- the Fan And CO2 Outputs PRIORITY MANAGEMENT
9- the Fan Output ON-DELAY
10- the Fan Output FAIL STATE
11- the (optional) AUX Fan Output FAIL STATE

1

FACTORY SETTING

ALTERNATE SETTING

CO2
ELEVATION

Sea level (or 0-ft elevation)

500-ft to 10 000-ft elevation in step of 500 feet.

2

FACTORY SETTING

ALTERNATE SETTING

FAN
OUTPUT
CONTROL

DIFFERENTIAL

Cooling only:

Starts +2°F above setpoint

Stops -2°F below setpoint

Cooling & Dehumidifying:

Starts +2°F OR +4% above setpoints

Stops -2°F below temp setpoint

AND

at humidity setpoints

Cooling only:

Starts +4°F above setpoint

Stops -4°F below setpoint

Cooling & Dehumidifying:

Starts +4°F OR +4% above setpoints

Stops -4°F below temp setpoint

AND

at humidity setpoints

(NOTE: See below Humidity Output Control Differential

to set alternate Humidity Differential value)

3

FACTORY SETTING

ALTERNATE SETTING

HUMIDITY
OUTPUT
CONTROL

DIFFERENTIAL

Dehumidifying:

Starts +4% above setpoint

Stops at setpoint

Humidifying:

Stops at setpoint

Starts -4% below setpoint

Dehumidifying:

Starts +8% above setpoint

Stops at setpoint

Humidifying:

Stops at setpoint

Starts -8% below setpoint

(NOTE: this alternate value will apply to

Cool & Dehumidify as well)