Grozone SCC1 Advanced User Guide – March 2012

www.grozonecontrol.com

10

FACTORY SETTING

ALTERNATE SETTING

FAN OUTPUT
FAIL STATE

The FAN Output is turned ON when a Temperature
Sensor Failure is detected, regardless of DAY and
NIGHT Temperature Setpoints.

The FAN Output is turned OFF when a Temperature
Sensor Failure is detected, regardless of DAY and
NIGHT Temperature Setpoints.


11

FACTORY SETTING

ALTERNATE SETTING

AUX FAN
OUTPUT
FAIL STATE

The AUX FAN Output (optional OB1-V) follows the
regular FAN Output (ON or OFF) in the event of a
Temperature Sensor Failure, regardless of DAY and
NIGHT Temperature Setpoints.

The AUX FAN Output (optional OB1-V) sets the
OB1-V at IDLE SPEED in the event of a Temperature
Sensor Failure, regardless of DAY and NIGHT
Temperature Setpoints. IDLE SPEED value is set
directly on OB1-V module through an adjustment on
the side of the enclosure.


ACCESSING THE

FACTORY / ALTERNATE SETTING EDIT MODE

Step 1- Follow the procedure to enter CO2 Sensor Calibration...

Day Enrichment Knob to CAL

Lock/Unlock Slide Switch to UNLOCK

HOLD pushbutton

...BUT YOU HAVE TO ABORT the Calibration AFTER 5 SECONDS (one blink per second)
by moving the Slide Switch back to the LOCK position. Then let the pushbutton go.


Step 2 - You are now given access to the FACTORY / ALTERNATE SETTING EDIT MODE.

TO EXIT this mode, simply return the Slide Switch to UNLOCK position.

Step 3 - The 11 settings that can be changed are grouped in 3 different PARAMETERS.

One PARAMETER can include up to 6 settings. Make sure to select the right PARAMETER
from these 3 choices.


SETTING NAME

PARAMETER TO EDIT

1

CO2 Elevation

CO2 ELEVATION

(SEE PAGE 10)

2

Fan Output Control Range (also called Differential)

OUTPUT CONTROL

(SEE PAGE 11)

3

Humidity Output Control Range (also called Differential)

4

CO2 Output Control Range (also called Differential)

5

Aux Heater Output Control Range (also called Differential)

6

LOW TEMPERATURE LIMIT

7

HIGH TEMPERATURE LIMIT

8

Fan And CO2 Outputs PRIORITY MANAGEMENT

PRIORITY AND FAIL

(SEE PAGE 12)

9

Fan Output ON-DELAY

10

Fan Output FAIL STATE

11

AUX Fan Output FAIL STATE (optional)