Sunlight Supply Grozone Control SCC1 Temperature, Humidity and CO2 Controller Simple One Series User Manual

Page 8

Advertising
background image

8 of 12

Grozone SCC1 Advanced User Guide – March 2012

www.grozonecontrol.com

4

FACTORY SETTING

ALTERNATE SETTING

CO2
OUTPUT
CONTROL

DIFFERENTIAL

DURING THE DAY ONLY

Stops on setpoint,

Starts -200 ppm below setpoint

DURING THE DAY ONLY

Stops on setpoint,

Starts -400 ppm below setpoint

5

FACTORY SETTING

ALTERNATE SETTING

AUX HEATER
OUTPUT
CONTROL

DIFFERENTIAL

Competing Equipment Auto Detection is NOT Set

Starts -8°F below setpoint, stops -2°F below setpoint

Competing Equipment Auto Detection is Set

Starts -8°F below setpoint, stops -2°F below setpoint

or

(*) Starts -12°F below setpoint, stops -6°F below setpoint

to avoid Fan and Heater to compete

(*) will use these values if Low Temp Limit set to Alternate Setting

6

FACTORY SETTING

ALTERNATE SETTING

LOW
TEMPERATURE
LIMIT

While using fan to cool & dehumidify, it stops the fan
if temperature reaches 6°F below setpoint even if it
is still too humid, to avoid freezing the crop. Limit
resets when temperature reaches setpoint.

While using fan to cool & dehumidify, it stops the fan
if temperature reaches 10°F below setpoint even if it
is still too humid, to avoid freezing the crop. Limit
resets when temperature reaches setpoint.


7

FACTORY SETTING

ALTERNATE SETTING

HIGH
TEMPERATURE
LIMIT

Relative to setpoint Temperature Limit:
While injecting CO2, CO2 output is stopped if the
temperature reaches 10°F above setpoint because of
excessive burner heat, then fan will restart
immediately. Limit resets when temperature reaches
setpoint.

Absolute Temperature Limit:
While injecting CO2, CO2 output is stopped if the
temperature reaches 90°F because of excessive burner
heat, then fan will restart immediately. Limit resets
when temperature reaches setpoint.

8

FACTORY SETTING

ALTERNATE SETTING

FAN AND CO2
OUTPUTS
PRIORITY
MANAGEMENT

(3 alternate settings)


The CO2 Output has a higher priority than the
FAN Output. The FAN stops when the CO2 output is
ON. FAN resumes operation following a ON-
DELAY
when CO2 Output turns OFF.

RESETTING THE ON_DELAY:
the ON-DELAY is reset to allow the FAN output to turn ON
immediately when CALIBRATION pushbutton is pressed during
normal operation.


The CO2 Output has a higher priority than the
FAN Output. The FAN stops when the CO2
output is ON. FAN resumes operation
immediately (NO DELAY) when CO2 Output
turns OFF.

The FAN Output has a higher priority than the
CO2 Output. The CO2 stops when the FAN
output is ON. CO2 resumes operation
immediately (NO DELAY) when FAN Output
turns OFF.

The CO2 and FAN Outputs work
independently.

9

FACTORY SETTING

ALTERNATE SETTING

FAN OUTPUT
ON-DELAY

(3 alternate settings)

The FAN Output ON-DELAY (started as soon as the
high priority CO2 output turns OFF) is 10 minutes.


RESETTING THE ON_DELAY:
the ON-DELAY is reset to allow the FAN output to turn ON
immediately when CALIBRATION pushbutton is pressed during
normal operation.

The FAN Output ON-DELAY (started as soon as the
high priority CO2 output turns OFF) is either

5 minutes.

20 minutes.

30 minutes