Specifications / 4. design and function, Design and function – WIKA TR10-J User Manual

Page 10

Advertising
background image

11208287.06 10/2013 GB/D/F/E

10

WIKA operating instructions resistance thermometers, thermocouples

GB

If these thermocouples cool too quickly (quicker than approx. 100 °C per hour), the undesirable

disordered crystal lattice occurs again during cooling in the range from approx. 600 °C to

approx. 400 °C. In the characteristic curve of type K, however, a consistently ordered alignment

state is assumed and provided with values. This results in a fault of thermoelectric voltage of up

to approx. 0.8 mV (approx. 5 °C) in this range. The K effect is reversible and is largely eliminated

again by annealing above 700 °C, followed by correspondingly slow cooling.

Thin sheathed thermocouples are particularly sensitive in this respect. Cooling in resting air can

already lead to deviations of 1 K.

In type N thermocouple, it has been possible to reduce this short-range-order effect by alloying

both legs with silicium.

The application range of these thermometers is limited both by the permissible maximum

temperature of the thermocouple and by the max. temperature of the thermowell material.

Listed models are available both as single or dual thermocouples. The thermocouple will be

delivered with an insulated measuring point, unless explicitly specified otherwise.

Tolerance value

For the tolerance value of thermocouples, a cold junction temperature of 0 °C has been taken as

the basis. When using a compensating cable or thermocouple cable, an additional measuring

error must be considered.

For limiting deviations and further specifications, see the corresponding WIKA data sheet and

technical information sheet IN 00.23, “Application of thermocouples”.

4. Design and function

4.1 Description

These thermometers (resistance thermometers and thermocouples) detect temperatures in

processes. These thermometers are suitable, depending on the version, for low, medium and high

process requirements.

They can be assembled as cable probes or as thermometers with a connection head. Optionally,

a temperature transmitter can be built into the connection head. For this temperature transmitter,

separate operating instructions will be enclosed.

Certain thermometer versions can be combined with a large number of thermowell designs.

Operation of these thermometers without a thermowell is only appropriate in special cases.