6. Commissioning, operation

6.2 Cable connections

The cable gland must be optimally sealed, to ensure that the required protection class is reached.

Requirements for meeting ingress protection

Only use cable glands within their indicated clamping range (cable diameter suitable for the

cable gland)

Do not use the lower clamping area with very soft cable types

Only use circular cross-section cables (if necessary, slightly oval in cross-section)

Do not twist the cable

Repeated opening/closing is possible; however only if necessary, as it might have a detrimental

effect on the protection class

For cable with a pronounced cold-flow behaviour the screw connection must be fully tightened

CAUTION!

The protection class is not valid with armoured cables (stainless steel sheathed)

Seal should be checked for signs of brittleness and, if necessary, replaced

6.3 Parallel threads

If the thermometer connecting head, extension neck, thermowell or process connection are

connected to parallel threads (e.g. G ½, M20 x 1.5 ...), these threads must be secured using seals

which prevent liquids from penetrating into the thermometer.

As standard, WIKA uses copper profile seals for the connection between the neck tube and the

thermowell, and flat paper seals for the connection of the connection head and the extension neck

or thermowell.

If the thermometer and the thermowell are already connected, the seals will already be mounted.

The plant operator must check whether the seals are suitable for the operating conditions and

must replace them, if necessary, with suitable seals.

For thermometers without a thermowell, and/or where these are delivered separately, the seals

are not included and must be ordered separately.

Tighten the threads by hand when carrying out the final assembly on the plant. This will

correspond to the delivery status of the premounted components. The final tightening torque

should be applied using a spanner (half rotation).

The seals must be replaced after dismantling!

The seals can be ordered from WIKA, indicating the WIKA order number and/or the

designation (see table).