6 model nomenclature, 0 specifications, 1 electrical specifications – Bard TCS22-***-003 User Manual

Page 11: 2 mechanical specifications, 3 environmental specifications, Model nomenclature, Specifications, Electrical specifications, Mechanical specifications, Environmental specifications

Advertising
background image

2100-444-003A

Page 5

1.6 Model

Nomenclature

TCS2 2 - H D M - 001

BASIC MODEL

SOFTWARE

REVISION NUMBER

---- REMOTE COMMUNICATIONS

SENSORS

DISPLAY M - With

H- Humidity & Temperature

D - With X - Without

T - Temperature Only X – Without

E - Ethernet

2.0 SPECIFICATIONS

2.1 Electrical

Specifications

Supply Voltage

208/240 VAC +/- 10% 50/60 HZ

Minimum Circuit Ampacity 3 Amp

Overcurrent Protection

Internal Circuit Breaker - 3 Amp

Controller Analog Inputs

16

Resolution

8 bits/ 0.4% Full Scale

Voltage Range

0 Vdc to +10 Vdc

Current Rating

5.0 mA at +10 Vdc


Binary Relay Outputs

12

Type

Form "A" Relay SPST N.O.

Contact Rating

24 VAC, 5 A Resistive

24

VAC,

2

A

Inductive

2.2 Mechanical

Specifications


Height

26.25

in.,

(667

mm.)

Width

17.00

in.,

(432

mm.)

Depth

5.50 in., (140 mm.)

Material

18 ga galvanized steel with Beige baked polyester enamel.

Mounting

Vertical

Mounting Area Required

27 in. high by 18 in. wide, (686 mm. high by 457 mm. wide)

Weight

27

lb.,

(12.3

kilograms)

2.3 Environmental

Specifications

Operating Temperature Range

32 to 130 o F (0 to 55

o

C)

Operating Humidity Range

10 to 95%, non condensing

Storage Temperature Range

-35 to 180 o F (-37 to 82

o

C)

Storage Humidity Range

5 to 95%, non condensing

Advertising