10 free cooling enthalpy setpoint, 11 free cooling dry bulb setpoint, Free cooling enthalpy setpoint – Bard TCS22-***-003 User Manual

Page 44: Free cooling dry bulb setpoint

Advertising
background image

2100-444-003A

Page 38

change. Anyone may view the setpoint value. The dehumidification setpoint range is from 50 to 65 %
RH. The default value is 50 % RH.


5.3.4.10

FREE COOLING ENTHALPY SETPOINT


The Enthalpy Setpoint is used to determine if the outside air is suitable to use for cooling the

structure. The default value for this point is 23.00 BTU/ lb. of dry air. Consult the Enthalpy Lookup
Table to adjust this value for the specific conditions that you wish to maintain in the structure. Read
down the relative humidity column under the percentage RH you wish to maintain. Read across the
inside temperature row to where it intersects the RH column. Enter this value into the Enthalpy Setpoint
Display. This will ensure that economizer will never bring in outside air that is too humid.

5.3.4.11

FREE COOLING DRY BULB SETPOINT


The Dry Bulb Setpoint is used to determine if the outside air is suitable to use for cooling the

structure. The default value for this point is 48 F

o

.This will ensure that the economizer will never bring

in outside air that is to warm to provide cooling.