2 unoccupied cooling setpoint, 3 occupied heating setpoint, 4 unoccupied heating setpoint – Bard TCS22-***-003 User Manual

Page 69: 5 high temperature alarm setpoint

Advertising
background image

2100-444-003A

Page 63

6.4.2.2 Unoccupied Cooling Setpoint

The Unoccupied Cooling Setpoint is the default cooling setpoint for a normally unoccupied

structure. Cooling of the Structure will begin if the zone temperature is above this setpoint.

The Unoccupied Cooling Setpoint will be the active setpoint whenever the occupied override has

not been started. The Unoccupied Cooling Setpoint may be adjusted by clicking the right or left arrows
next to the Unoccupied Cooling Setpoint Text box. Clicking on the right arrow will increase the
Unoccupied Cooling Setpoint by 0.50 degrees Fahrenheit until the maximum allowed setpoint of 85.0
degrees is reached. Clicking on the left arrow will decrease the Unoccupied Cooling Setpoint by 0.50
degrees Fahrenheit until the minimum allowed setpoint of 72.0 degrees is reached.

6.4.2.3 Occupied Heating Setpoint


The Occupied Heating Setpoint is used to raise the heating setpoint to a higher temperature if the

structure is occupied. The Occupied Heating Setpoint will be the active setpoint if the occupancy
override timer has been triggered and if the zone temperature is below the Occupied Heating Setpoint.
Once the occupied timer is started the Occupied Heating Setpoint will be active for two (2) Hours and
then will reset to the Unoccupied Heating Setpoint. Occupancy override can be canceled after 5 minutes
by pressing the occupancy override button again.

Next to the Occupied Heating Setpoint value is a scroll bar. Clicking on the right arrow will

increase the Occupied Heating Setpoint by 0.50 degrees Fahrenheit until the maximum allowed setpoint
of 70.0 degrees is reached. Clicking on the left arrow will decrease the Occupied Heating Setpoint by
0.50 degrees Fahrenheit until the minimum allowed setpoint of 68.0 degrees is reached.

6.4.2.4 Unoccupied Heating Setpoint


The Unoccupied Heating Setpoint is the default heating setpoint for a normally unoccupied

structure. Heating of the structure will begin if the zone temperature is below this setpoint.

The Unoccupied Heating Setpoint will be the active setpoint whenever the Occupied Override

has not been started. The Unoccupied Heating Setpoint may be adjusted by clicking the right or left
arrows next to the Unoccupied Heating Setpoint text box. Clicking on the right arrow will increase the
Unoccupied Heating Setpoint by 0.50 degrees Fahrenheit until the maximum allowed setpoint of 70.0
Degrees is reached. Clicking on the left arrow will decrease the Unoccupied Heating Setpoint by 0.50
degrees Fahrenheit until the minimum allowed setpoint of 60.0 degrees is reached.

6.4.2.5 High Temperature Alarm SetPoint


The High Alarm Setpoint is the temperature at which the high temperature alarm will trigger for

the structure. If the zone temperature of the structure exceeds the High Alarm Setpoint then an alarm
event is logged in the alarm log and a shelter alarm is generated.

Next to the High Temperature Alarm value is a scroll bar. Clicking on the right arrow will

increase the High Temperature Alarm Setpoint by 0.50 degrees Fahrenheit until the maximum allowed
setpoint of 100.0 degrees is reached. Clicking on the left arrow will decrease the High Temperature