2100-444-003A

Page 83

7. MAINTENANCE & TROUBLESHOOTING

7.1 Routine

Maintenance


The TCS22 requires minimal maintenance. Once every 4 years replace the battery under the

controller cover. This battery powers the hardware clock during power outages.

Check sensor calibration once every two years.


7.2 Troubleshooting

7.2.1 TCS22 TROUBLESHOOTING

Problem

Check Out Points

Procedure

TCS22 Fails to operate

Check 240 Volt Power

Check TCS22 Circuit breaker

Check 24 Volt Power

Remove power connector from
controller and Check for 24 volt Power
from pin 1 to pin 3 on plug

Check Internal Fuse

Remove screws from the four corner of
the front panel of the controller. The
fuse is located in upper left hand corner
of the controller.

Blower #1 light is On but
Blower fails to operate

Check A/C unit 24 Volt power
from C to G

Check controller switch

Remove junction connector J5. Check
for continuity from pin #3 to pin #6 on
controller with the Blower light ON.

Check wiring and connections

Compressor #1 light is On but
Compressor fails to operate

Check A/C unit 24 Volt power
from C to Y

Check controller switch

Remove junction connector J5. Check
for continuity from pin #2 to pin #5 on
controller with the Compressor light
ON.

Check wiring and connections

Heater #1 light is On but
Heater fails to operate

Check A/C unit 24 Volt power
from C to W1

Check controller switch

Remove junction connector J5. Check
for continuity from pin #8 to pin #11 on
controller with the Compressor light
ON.

Check wiring and connections

Economizer #1 light is On but
Economizer fails to operate

Check controller switch

Disconnect E from the terminal strip on
the TCS22. Check for continuity from E