2100-444-003A

Page 34

5.3.3.7

FIRE TROUBLE


The Fire Trouble alarm item monitors the fire alarm system in the structure. A "None" alarm

message indicates that no alarm is present and that the fire alarm system is operating normally. A "Fault"
alarm message indicates that an alarm is present and the fire alarm system is malfunctioning.

This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This

is a medium priority alarm.

5.3.3.8

FIRE ALARM


The Fire Alarm item monitors the fire alarm system in the structure. A "None" alarm message

indicates that no alarm is present and that the fire alarm system has not detected a fire. A "Fault" alarm
message indicates that an alarm is present and that the fire alarm system has detected a fire in the
structure.

This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This

is a critical priority alarm.

5.3.3.9

OUTDOOR TEMP ALARM


The Outdoor temperature alarm item will show one of two different alarm messages. A No alarm

message indicates that the Outdoor Temperature Sensor is functioning normally. A Fault alarm message
indicates that the Outdoor Temperature Sensor is sensing a value above 120 F

o

or below -20 F

o

. This

probably indicates a faulty sensor.

These are all self-clearing alarms and will reset themselves when the alarm condition no longer

exists. This is a critical alarm.

5.3.3.10

OUTDOOR HUMIDITY ALARM


The Outdoor Humidity Alarm item will show one of two different alarm messages. A No alarm

message indicates that the Outdoor Humidity Sensor is functioning normally. A Fault alarm message
indicates that the Outdoor Humidity Sensor is sensing a value above 99 % RH or below 2 % RH. This
probably indicates a faulty sensor. When a Outdoor Humidity Fault alarm is detected, the Outdoor
Humidity value defaults to 50 % RH until the sensor is replaced.

These are all self-clearing alarms and will reset themselves when the alarm condition no longer

exists. This is a medium priority alarm.

5.3.3.11 DOOR

ALARM


The Door Alarm item monitors the door switch in the structure. A "None" alarm message

indicates that no alarm is present and that the door is closed. A "Fault" alarm message indicates that an
alarm is present and that the door in the structure is open.

This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This

is a critical priority alarm.