1 occupied cooling setpoint, 2 unoccupied cooling setpoint, Occupied cooling setpoint – Bard TCS22-***-003 User Manual
Page 42: Unoccupied cooling setpoint
2100-444-003A
Page 36
5.3.4.1 OCCUPIED COOLING SETPOINT
The occupied cooling setpoint requires an authority level of Supervisor or higher to change.
Anyone may view the setpoint value. The Occupied Cooling Setpoint Range is from 72.0 to 80.0 F
o
. The
default value is 75.0 F
o
5.3.4.2 UNOCCUPIED COOLING SETPOINT
The unoccupied cooling setpoint requires an authority level of Supervisor or higher to change.
Anyone may view the setpoint value. The Unoccupied Cooling Setpoint Range is from 72.0 to 85.0 F
o
.
The default value is 80.0 F
o
SETPOINTS
F1 = EDIT MODE
ENTER TO EDIT
Occ. Cooling SP
75.00 F
Unocc. Clg. SP
80.00 F
Occ. Heating SP
70.00 F
Unocc. Htg. SP
68.00 F
Hi Temp Alarm SP
87.00 F
Lo Temp Alarm SP
56.00 F
Hi Humidity SP
80.0 RH
Low Humidity SP
20.0 RH
Dehum. Setpoint
60.0 RH
FC Enth Setpoint
23.00 BTU/LB
FC DB Setpoint
48.00 F