4 sensor specifications, 1 temperature sensors, 2 humidity sensors – Bard TCS22-***-003 User Manual

Page 12: 3 compressor current sensor, 4 dirty filter sensor, Sensor specifications, 1 temperature, Sensors, 2 humidity, Compressor current sensor

Advertising
background image

2100-444-003A

Page 6

2.4 Sensor

Specifications

2.4.1 TEMPERATURE

SENSORS

Indoor

and

Outdoor


Type

Thermistor

Ohms

3000

at 77

o

F (25

o

C)

Temperature

Range

-40

to

302

o

F (-40 to 150

o

C

)

Interchangeability

.2

Deg

Celsius


Discharge


Type

Thermistor

Ohms

10000

at 77

o

F (25

o

C)

Temperature

Range

-40

to

302

o

F (-40 to 150

o

C

)

Interchangeability

.2

Deg

Celsius

2.4.2

HUMIDITY

SENSORS

Type

Bulk

Polymer

Output

0-5

Vdc

Supply Voltage

24 Vac, +/- 15%

Accuracy

+/-

5%

Sensitivity

0.1%

RH

Repeatability

0.5%

RH

Long Term Stability

Less than 1% per year

Interchangeability

+/-

3%

Temperature Range

-40 to 130 o F (-40 to 76

o

C)

Humidity Range

0 to 99%, non condensing

2.4.3 COMPRESSOR CURRENT SENSOR
Type

Solid

State

DC

Switch

Output

Form

"A"

solid

state

DC

switch

Supply

Voltage Self

Powered

Trip Current Range

1 to 175 Amps

Maximum Load

150 mA, at 30 VDC

Temperature Range

-58 to 149 o F (-50 to 65

o

C)

Dimensions

2.125 in. high, 3.25 in. wide, 1 in. deep

(54 mm. high, 83 mm. wide, 26 mm. deep)

2.4.4 DIRTY FILTER SENSOR
Type

Mechanical

Airflow

Switch

Output

Form

"A"

Contact

Supply

Voltage Self

Powered

Maximum Load

1.5A, at 24 VAC

Temperature Range

0 to 170 o F (-18 to 77

o

C)

Pressure Range

0.1 to 0.7 in. wc.

Dimensions

3 1/4 in. high, 2 1/4 in. wide, 2 in. deep

(83 mm. high, 57 mm. wide, 51 mm. deep)

Advertising