Table 5 – HEATING RATING TABLE -- LOW NO

x

1

UNIT

GAS HEAT

LOW NOx HEAT EXCHANGER

TEMP RISE

(DEG F)

THERMAL

EFFICIENCY

(%)

AFUE

(%)

INPUT / OUTPUT

STAGE 1 (MBH)

INPUT / OUTPUT

STAGE 2 (MBH)

Sin

gle

Pha

se

04

LOW

---

60 / 50

20 --- 50

81%

80%

MED

---

90 / 74

30 --- 60

81%

81%

HIGH

---

---

---

---

---

05

LOW

---

60 / 50

20 --- 50

81%

80%

MED

---

90 / 74

30 --- 60

81%

81%

HIGH

---

120 / 101

40 --- 70

81%

80%

06

LOW

---

60 / 50

15 --- 50

81%

80%

MED

---

90 / 74

25 --- 60

80%

81%

HIGH

---

120 / 101

35 --- 70

80%

81%

Th

re

e

P

ha

se

04

LOW

---

60 / 50

20 --- 50

81%

80%

MED

---

90 / 74

30 --- 60

81%

81%

HIGH

---

---

---

---

---

05

LOW

---

60 / 50

20 --- 50

81%

80%

MED

---

90 / 74

30 --- 60

81%

81%

HIGH

---

120 / 101

40 --- 70

81%

80%

06

LOW

---

60 / 50

15 --- 50

81%

80%

MED

---

90 / 74

25 --- 60

80%

81%

HIGH

---

120 / 101

35 --- 70

80%

81%

NOTE:

1. Units meet California’s South Coast Air Quality Management District (SCAQMD) Low---NO

x

emissions requirement of 40

nanograms per joule or less.

Table 6 – SOUND PERFORMANCE TABLE

UNIT

COOLING

STAGES

OUTDOOR SOUND (dB)

A---WEIGHTED

63

125

250

500

1000

2000

4000

8000

04A

1

80

90.6

80.9

80.2

76

74.6

71.3

68.5

63.9

05A

1

81

90.9

84.6

79.5

77.9

76.5

71.1

66.9

62.5

06A

1

78

84.0

82.2

76.3

74.8

72.5

68.8

65.6

61.8

07A

1

78

88.8

81.8

76.9

74.4

73.3

69.8

66.3

62.7

08A

1

82

90.1

82.6

81.0

79.4

77.0

73.0

70.4

66.7

08D

2

82

85.8

84.3

80.5

78.7

76.4

72.7

68.3

65.1

09A

1

83

91.2

86.4

81.9

81.0

78.3

73.9

71.4

67.3

09D

2

82

88.6

85.0

81.6

79.5

77.4

74.1

71.0

66.3

12A

1

82

88.6

85.0

81.6

79.5

77.4

74.1

71.0

66.3

12D

2

82

89.0

83.1

80.5

78.5

75.5

71.6

69.6

69.3

14D

2

87

87.0

85.2

84.6

84.9

82.2

78.4

75.3

72.9

LEGEND

dB --- Decibel

NOTES:

1. Outdoor sound data is measure in accordance with

AHRI standard 270---2008.

2. Measurements are expressed in terms of sound power.

Do not compare these values to sound pressure values

because sound pressure depends on specific environ-

mental factors which normally do not match individual

applications. Sound power values are independent of

the environment and therefore more accurate.

3. A---weighted sound ratings filter out very high and very

low frequencies, to better approximate the response of

“average” human ear. A---weighted measurements for

Bryant units are taken in accordance with AHRI stand-

ard 270---2008.

580J

Advertising