Fan performance (cont.) – Bryant LEGACY LINE 580J User Manual

Page 57

Advertising
background image

57

FAN PERFORMANCE (cont.)

Table 49 – 580J*09

3 PHASE

8.5 TON HORIZONTAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Field---Supplied Drive

1

Standard Static Option

Medium Static Option

2550

497

0.48

579

0.61

651

0.75

717

0.90

777

1.05

2763

524

0.58

602

0.72

671

0.87

735

1.03

794

1.19

2975

551

0.70

626

0.86

693

1.01

754

1.18

812

1.35

3188

580

0.84

651

1.00

716

1.17

775

1.34

831

1.52

3400

609

1.00

677

1.17

739

1.35

797

1.53

851

1.71

3613

638

1.17

703

1.35

763

1.54

819

1.73

871

1.93

3825

668

1.37

730

1.56

788

1.76

842

1.96

893

2.16

4038

698

1.59

758

1.79

813

2.00

866

2.20

915

2.42

4250

728

1.83

786

2.04

839

2.26

890

2.47

938

2.70

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

High Static Option

2550

833

1.21

886

1.38

936

1.56

984

1.74

1029

1.93

2763

849

1.36

900

1.53

950

1.72

996

1.90

1041

2.10

2975

865

1.52

916

1.70

964

1.89

1010

2.09

1054

2.29

3188

883

1.70

933

1.89

980

2.09

1025

2.29

1068

2.50

3400

902

1.90

950

2.10

996

2.30

1041

2.51

1083

2.73

3613

921

2.13

969

2.33

1014

2.54

1057

2.76

1099

2.98

2

3825

941

2.37

988

2.58

1032

2.80

1075

3.02

1116

3.25

4038

963

2.63

1008

2.86

1051

3.08

1093

3.31

1133

3.55

4250

984

2.92

1029

3.15

1071

3.39

1112

3.63

1152

3.87

NOTE: For more information, see General Fan Performance Notes.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied fan pulley (part no. KR11AK012) and belt (part no. KR29AF055).
2. Recommend using field---supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).

Table 50 – 580J*09

3 PHASE

8.5 TON VERTICAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Standard Static Option

Medium Static Option

2550

526

0.51

600

0.65

666

0.79

727

0.93

783

1.07

2763

557

0.62

627

0.77

690

0.92

749

1.08

804

1.23

2975

588

0.75

655

0.91

716

1.08

772

1.24

825

1.40

3188

621

0.90

684

1.07

743

1.25

797

1.42

848

1.60

3400

653

1.06

714

1.25

770

1.44

822

1.62

872

1.81

3613

687

1.25

744

1.45

798

1.65

849

1.84

897

2.04

3825

720

1.45

775

1.67

827

1.88

876

2.09

922

2.30

4038

754

1.69

807

1.91

856

2.13

904

2.35

949

2.57

4250

788

1.94

839

2.17

886

2.41

932

2.64

976

2.88

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

High Static Option

2550

836

1.20

886

1.34

934

1.48

979

1.61

1022

1.74

2763

855

1.37

904

1.52

950

1.67

995

1.82

1037

1.97

2975

875

1.56

923

1.72

968

1.88

1012

2.04

1053

2.20

3188

897

1.77

943

1.94

987

2.11

1030

2.29

1071

2.46

3400

919

1.99

964

2.18

1007

2.36

1049

2.55

1089

2.73

1

3613

943

2.24

986

2.44

1029

2.63

1069

2.83

1108

3.02

3825

967

2.51

1010

2.71

1051

2.92

1090

3.13

1129

3.34

4038

992

2.80

1034

3.02

1074

3.24

1112

3.46

1150

3.68

4250

1018

3.11

1058

3.34

1097

3.57

---

---

---

---

NOTE: For more information, see General Fan Performance Notes.

Boldface indicates field supplied drive is required.

1. Recommend using field supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).

580J

Advertising