Bryant LEGACY LINE 580J User Manual

Page 47

Advertising
background image

47

Table 31 – COOLING CAPACITIES

2--STAGE COOLING (RTPF ONLY)

12.5 TONS

580J14 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

TEMP (F) AIR ENT

CONDENSER (Edb)

AIR ENTERING EVAPORATOR --- CFM

3750/0.02

5000/0.06

6250/0.05

Air Entering Evaporator --- Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

183.66

166.86

151.43

194.90

177.83

162.05

201.97

184.84

170.53

SHC

79.39

100.52

121.91

91.70

119.42

147.05

102.94

137.00

166.71

kW

9.82

9.63

9.46

9.58

9.76

9.96

10.04

9.84

9.67

85

TC

172.71

156.78

142.09

183.32

167.13

152.17

189.98

173.73

160.25

SHC

69.03

90.92

112.95

80.69

109.17

137.51

91.49

126.33

156.65

kW

10.82

10.63

10.45

10.57

10.76

10.96

11.04

10.84

10.67

95

TC

161.37

146.24

132.38

171.36

156.04

141.86

177.62

162.22

149.50

SHC

58.44

81.04

103.77

69.42

98.67

127.71

79.83

115.45

146.15

kW

11.92

11.73

11.56

11.68

11.86

12.05

12.14

11.93

11.77

105

TC

149.57

135.32

122.21

158.89

144.45

131.10

164.74

150.27

138.35

SHC

47.57

70.92

94.32

57.85

87.91

117.61

67.79

104.26

135.30

kW

13.12

12.94

12.77

12.89

13.06

13.24

13.32

13.13

12.97

115

TC

137.22

123.88

111.55

145.85

132.33

119.84

151.27

137.71

126.67

SHC

36.31

60.47

84.57

45.87

76.77

107.19

55.34

92.66

123.98

kW

14.41

14.25

14.10

14.20

14.35

14.53

14.59

14.42

14.28

580J14 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

TEMP (F)AIR ENT

CONDENSER(Edb)

AIR ENTERING EVAPORATOR --- Ewb (F)

75 Dry Bulb

62.5 Wet Bulb

(50% Relative)

75 Dry Bulb

64 Wet Bulb

(56% Relative)

75 Dry Bulb

65.3 Wet Bulb

(60% Relative)

Air Entering Evaporator --- Cfm

3750

5000

6250

3750

5000

6250

3750

5000

6250

80

TC

52.42

45.88

36.99

62.64

58.07

51.07

71.56

68.64

63.23

SHC

---0.39

---0.54

---0.67

---0.31

---0.46

---0.58

---0.26

---0.40

---0.52

kW

9.65

9.39

9.07

9.97

9.77

9.50

10.25

10.11

9.89

75

TC

53.45

46.63

36.10

63.77

59.11

51.87

72.76

69.80

64.31

SHC

0.59

0.44

0.30

0.67

0.52

0.40

0.72

0.58

0.47

kW

9.09

8.83

8.49

9.39

9.20

8.94

9.67

9.53

9.32

70

TC

54.33

46.91

37.58

64.77

60.01

52.30

73.80

70.80

65.24

SHC

1.56

1.41

1.29

1.64

1.50

1.38

1.70

1.56

1.45

kW

8.81

8.53

8.62

9.15

8.94

8.65

9.46

9.31

9.08

60

TC

55.47

49.48

40.48

66.62

62.07

54.88

75.68

72.76

67.28

SHC

3.50

3.38

3.27

3.59

3.47

3.36

3.65

3.52

3.42

kW

8.36

8.84

8.98

9.88

9.56

9.10

9.83

9.64

9.31

50

TC

58.33

51.72

42.81

68.72

63.93

55.84

77.74

74.77

69.24

SHC

5.47

5.35

5.24

5.54

5.43

5.32

5.60

5.49

5.39

kW

8.98

9.25

9.43

9.33

8.97

8.73

9.55

9.33

9.70

40

TC

60.33

53.69

46.89

70.67

65.93

49.83

79.46

76.62

71.24

SHC

7.42

7.31

7.22

7.49

7.39

7.23

7.55

7.45

7.37

kW

9.16

9.88

9.06

9.50

9.05

9.47

10.31

10.00

9.48

NOTE: Perfect Humidity only available on 2---stage RTPF models.

LEGEND
Edb
--- Entering Dry---Bulb
Ewb --- Entering Wet---Bulb
kW

--- Compressor Motor Power Input

Idb

--- Leaving Dry---Bulb

Iwb --- Leaving Wet---Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC

--- Total Capacity (1000 Btuh) Gross

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet---bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

Where: h

ewb

= Enthalpy of air entering evaporator coil

580J

Advertising