Bryant LEGACY LINE 580J User Manual

Page 39

Advertising
background image

39

Table 23 – COOLING CAPACITIES

2--STAGE COOLING (RTPF ONLY)

7.5 TONS

580J08 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

TEMP (F) AIR ENT

CONDENSER (Edb)

AIR ENTERING EVAPORATOR --- CFM

2250/0.05

3000/0.07

3750/0.09

Air Entering Evaporator --- Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

103.05

93.02

83.60

109.77

99.52

90.08

114.01

103.69

95.19

SHC

43.66

55.34

67.09

50.99

66.29

81.31

57.49

76.27

92.20

kW

4.90

4.83

4.77

4.82

4.88

4.96

4.99

4.91

4.85

85

TC

95.39

85.83

76.88

101.59

91.89

82.95

105.53

95.76

87.77

SHC

36.42

48.47

60.60

43.24

58.99

74.40

49.44

68.68

84.90

kW

5.49

5.42

5.36

5.40

5.47

5.54

5.58

5.50

5.44

95

TC

87.48

78.44

69.97

93.21

84.05

75.61

96.84

87.63

80.14

SHC

28.98

41.46

53.97

35.32

51.53

67.34

41.21

60.92

77.41

kW

6.16

6.09

6.03

6.08

6.14

6.21

6.24

6.17

6.11

105

TC

79.35

70.83

62.84

84.57

75.96

68.04

87.88

79.23

72.26

SHC

21.34

34.26

47.18

27.17

43.86

60.08

32.73

52.95

69.70

kW

6.93

6.86

6.81

6.85

6.91

6.97

7.00

6.93

6.88

115

TC

70.87

62.89

55.42

75.58

67.54

60.15

78.56

70.51

64.06

SHC

13.40

26.79

40.14

18.70

35.89

52.54

23.94

44.68

61.67

kW

7.79

7.74

7.69

7.73

7.78

7.83

7.86

7.80

7.76

580J08 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

TEMP (F) AIR ENT

CONDENSER (Edb)

AIR ENTERING EVAPORATOR --- Ewb (F)

75 Dry Bulb

62.5 Wet Bulb

(50% Relative)

75 Dry Bulb

64 Wet Bulb

(56% Relative)

75 Dry Bulb

65.3 Wet Bulb

(60% Relative)

Air Entering Evaporator --- Cfm

2250

3000

3750

2250

3000

3750

2250

3000

3750

80

TC

27.60

32.75

30.19

40.09

39.43

37.73

45.06

45.25

44.25

SHC

---3.12

5.20

6.71

3.75

5.24

6.75

3.77

5.26

6.78

kW

4.56

4.51

4.46

4.63

4.60

4.56

4.70

4.67

4.64

75

TC

35.40

33.78

31.20

41.14

40.51

38.80

46.15

46.37

45.38

SHC

4.67

6.17

7.69

4.71

6.21

7.73

4.74

6.24

7.76

kW

4.41

4.36

4.39

4.41

4.36

4.36

4.41

4.39

4.36

70

TC

36.36

34.71

32.18

42.10

41.47

39.77

47.08

47.31

46.32

SHC

5.63

7.14

8.66

5.67

7.18

8.71

5.70

7.21

8.74

kW

4.43

4.49

4.41

4.44

4.40

4.39

4.49

4.47

4.44

60

TC

38.25

36.64

34.15

43.97

43.37

41.72

48.98

49.22

48.26

SHC

7.56

9.09

10.62

7.60

9.13

10.66

7.62

9.15

10.69

kW

4.56

4.55

4.43

4.57

4.53

4.46

4.56

4.55

4.50

50

TC

40.15

38.60

36.14

45.95

45.37

43.73

50.57

50.97

49.56

SHC

9.48

11.03

12.58

9.52

11.07

12.62

9.54

11.10

12.64

kW

4.63

4.52

4.38

4.45

4.41

4.33

5.25

4.91

5.60

40

TC

42.18

40.62

38.11

47.80

47.25

45.43

52.65

52.75

51.83

SHC

11.41

12.98

14.54

11.45

13.02

14.58

11.47

13.04

14.60

kW

4.32

4.37

4.37

4.65

4.60

4.89

4.96

5.20

5.12

NOTE: Perfect Humidity only available on 2---stage RTPF models.

LEGEND
Edb
--- Entering Dry---Bulb
Ewb --- Entering Wet---Bulb
kW

--- Compressor Motor Power Input

Idb

--- Leaving Dry---Bulb

Iwb --- Leaving Wet---Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC

--- Total Capacity (1000 Btuh) Gross

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet---bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

Where: h

ewb

= Enthalpy of air entering evaporator coil

580J