Curbs & weights dimensions j*04 (cont.) – Bryant LEGACY LINE 580J User Manual

Page 18

Advertising
background image

18

CURBS & WEIGHTS DIMENSIONS -- 580J*04--07 (cont.)

C08599

Fig. 2 -- Dimensions 580J 04--07

C

B

A

D

C08337

Fig. 3 -- Service Clearance

LOC

DIMENSION

CONDITION

A

48---in (1219 mm)

Unit disconnect is mounted on panel

18---in (457 mm)

No disconnect, convenience outlet option

18---in (457 mm)

Recommended service clearance

12---in (305 mm)

Minimum clearance

B

42---in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall)

36---in (914 mm)

Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)

Special

Check for sources of flue products within 10---ft of unit fresh air intake hood

C

36---in (914 mm)

Side condensate drain is used

18---in (457 mm)

Minimum clearance

D

48---in (1219 mm)

No flue discharge accessory installed, surface is combustible material

42---in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36---in (914 mm)

Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)

Special

Check for adjacent units or building fresh air intakes within 10---ft of this unit’s flue outlet

580J