Table 9 – PHYSICAL DATA

(HEATING)

3 -- 6 TONS

580J*04

580J*05

580J*06

580J*07

Gas Connection

# of Gas Valves

1

1

1

1

Nat. gas supply line press (in. w.g.)/(PSIG)

4 ---13 / 0.18 --- 0.47

4 ---13 / 0.18 --- 0.47

4 ---13 / 0.18 --- 0.47

4 ---13 / 0.18 --- 0.47

Propane supply line press (in. w.g.)/(PSIG)

11 ---13 / 0.40 --- 0.47

11 ---13 / 0.40 --- 0.47

11 ---13 / 0.40 --- 0.47

11 ---13 / 0.40 --- 0.47

Heat Anticipator Setting (Amps)

1st stage

0.14

0.14

0.14

0.14

2nd stage

0.14

0.14

0.14

0.14

Natural Gas, Propane Heat

# of stages / # of burners (total)

1 / 2

1 / 2

1 / 2

1 / 2

LO

W

Connection size

1/2---in NPT

1/2---in NPT

1/2---in NPT

1/2---in NPT

Rollout switch opens / closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise range (F)

25 --- 55

25 --- 55

20 --- 55

15 --- 55

# of stages / # of burners (total)

1 or 2 / 3

1 / 3

1 / 3

1 / 3

MED

Connection size

1/2---in NPT

1/2---in NPT

1/2---in NPT

1/2---in NPT

Rollout switch opens / closes

195 / 115

195 / 115

195 / 115

195 / 115

Temperature rise range (F)

55 --- 85

35 --- 65

30 --- 65

25 --- 65

# of stages / # of burners (total)

---

1 or 2 / 3

1 or 2 / 3

1 or 2 / 3

HI

G

H

Connection size

---

1/2---in NPT

1/2---in NPT

1/2---in NPT

Rollout switch opens / closes

---

195 / 115

195 / 115

195 / 115

Temperature rise range (F)

---

50 --- 80

40 --- 80

35 --- 80

Low NO

x

Gas Heat

# of stages / # of burners (total)

1 / 2

1 / 2

1 / 2

---

LO

W

Connection size

1/2---in NPT

1/2---in NPT

1/2---in NPT

---

Rollout switch opens / closes

195 / 115

195 / 115

195 / 115

---

Temperature rise range (F)

20 --- 50

20 --- 50

15 --- 50

---

# of stages / # of burners (total)

1 / 3

1 / 3

1 / 3

---

MED

Connection size

1/2---in NPT

1/2---in NPT

1/2---in NPT

---

Rollout switch opens / closes

195 / 115

195 / 115

195 / 115

---

Temperature rise range (F)

30 --- 60

30 --- 60

25 --- 60

---
---

# of stages / # of burners (total)

---

1 / 3

1 / 3

---

HI

G

H

Connection size

---

1/2---in NPT

1/2---in NPT

---

Rollout switch opens / closes

---

195 / 115

195 / 115

---

Temperature rise range (F)

---

40 --- 70

35 --- 70

---

580J