Table 16 – COOLING CAPACITIES

1--STAGE COOLING

4 TONS

580J05 (4 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

Air Entering Evaporator --- CFM

Temp (F) Air Ent

Condenser (Edb)

80 dry bulb

80 dry bulb

80 dry bulb

72 wet bulb

67 wet bulb

62 wet bulb

1200

1600

2000

1200

1600

2000

1200

1600

2000

75

TC

52.5

55.9

58.6

47.1

50.2

52.7

41.7

44.5

46.8

SHC

22.6

25.5

27.8

27.1

29.9

32.0

31.6

34.2

36.2

kW

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

85

TC

48.7

52.2

54.9

43.4

46.5

49.0

38.0

40.8

43.1

SHC

18.0

21.3

23.9

23.6

26.8

29.2

29.3

32.2

34.4

kW

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

95

TC

44.9

48.4

51.2

39.6

42.8

45.3

34.3

37.1

39.4

SHC

13.4

17.2

20.0

20.2

23.7

26.4

27.0

30.2

32.7

kW

3.4

3.4

3.4

3.3

3.3

3.3

3.3

3.3

3.3

105

TC

41.1

44.7

47.5

35.9

39.1

41.7

30.6

33.5

35.8

SHC

8.8

13.0

16.1

16.7

20.6

23.6

24.6

28.2

31.0

kW

3.8

3.8

3.8

3.7

3.7

3.7

3.7

3.7

3.7

115

TC

37.4

41.0

43.9

32.1

35.4

38.0

26.8

29.8

32.1

SHC

4.3

8.8

12.2

13.3

17.5

20.7

22.3

26.2

29.2

kW

4.2

4.2

4.2

4.2

4.2

4.2

4.1

4.1

4.1

580J05 (4 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

Air Entering Evaporator --- CFM

Temp (F) Air Ent

Condenser (Edb)

75 dry bulb

75 dry bulb

75 dry bulb

62.5 wet bulb (50% relative)

64 wet bulb (55% relative)

65.3 wet bulb (60% relative)

1200

1600

2000

1200

1600

2000

1200

1600

2000

80

TC

11.6

13.8

15.5

13.5

15.8

17.6

15.2

17.5

19.3

SHC

---1.0

1.2

3.0

---3.1

---0.8

0.9

---4.8

---2.6

---0.9

kW

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

75

TC

12.5

14.6

16.2

14.3

16.4

18.1

15.9

18.1

19.8

SHC

---0.7

1.4

3.0

---2.7

---0.6

1.1

---4.3

---2.2

---0.6

kW

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

70

TC

13.4

15.3

16.8

15.1

17.1

18.7

16.6

18.7

20.3

SHC

---0.5

1.5

3.0

---2.3

---0.3

1.2

---3.8

---1.9

---0.3

kW

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

60

TC

15.1

16.8

18.1

16.7

18.4

19.8

18.1

19.9

21.2

SHC

0.0

1.7

3.1

---1.5

0.2

1.5

---2.8

---1.1

0.2

kW

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

50

TC

16.9

18.3

19.4

18.3

19.8

20.9

19.6

21.0

22.2

SHC

0.6

2.0

3.1

---0.7

0.7

1.8

---1.8

---0.4

0.7

kW

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

40

TC

18.7

19.8

20.7

19.9

21.1

22.0

21.0

22.2

23.2

SHC

1.1

2.2

3.1

0.1

1.2

2.1

---0.8

0.4

1.3

kW

2.6

2.6

2.6

2.7

2.7

2.7

2.7

2.7

2.7

LEGEND
Edb
--- Entering Dry---Bulb
Ewb --- Entering Wet---Bulb
kW

--- Compressor Motor Power Input

Idb

--- Leaving Dry---Bulb

Iwb --- Leaving Wet---Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC

--- Total Capacity (1000 Btuh) Gross

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet---bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm