Table 18 – COOLING CAPACITIES

1--STAGE COOLING

5 TONS

580J06 (5 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

Air Entering Evaporator --- CFM

Temp (F) Air Ent

Condenser (Edb)

80 dry bulb

80 dry bulb

80 dry bulb

72 wet bulb

67 wet bulb

62 wet bulb

1750

2000

2250

1750

2000

2250

1750

2000

2250

75

TC

73.1

78.7

84.5

63.2

66.9

70.8

53.2

55.1

57.1

SHC

35.3

37.2

38.8

42.0

43.7

45.3

48.7

50.3

51.8

kW

3.3

3.3

3.3

3.3

3.3

3.3

3.3

3.3

3.3

85

TC

67.6

71.2

75.0

59.1

61.2

63.3

50.6

51.1

51.5

SHC

27.9

30.0

31.9

36.3

38.3

40.1

44.8

46.6

48.2

kW

3.8

3.8

3.8

3.8

3.8

3.8

3.8

3.8

3.8

95

TC

62.1

63.8

65.5

55.1

55.4

55.8

48.0

47.0

46.0

SHC

20.5

22.9

24.9

30.7

32.9

34.8

40.9

42.9

44.7

kW

4.3

4.3

4.3

4.3

4.3

4.3

4.3

4.3

4.3

105

TC

56.6

56.3

56.0

51.0

49.6

48.3

45.4

43.0

40.5

SHC

13.1

15.7

18.0

25.0

27.5

29.6

36.9

39.2

41.2

kW

4.8

4.8

4.8

4.8

4.8

4.8

4.7

4.7

4.7

115

TC

51.1

48.8

46.5

46.9

43.9

40.7

42.8

39.0

35.0

SHC

5.8

8.6

11.0

19.4

22.0

24.4

33.0

35.5

37.7

kW

5.3

5.3

5.3

5.3

5.3

5.3

5.2

5.2

5.2

580J06 (5 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

Air Entering Evaporator --- CFM

Temp (F) Air Ent

Condenser (Edb)

75 dry bulb

75 dry bulb

75 dry bulb

62.5 wet bulb (50% relative)

64 wet bulb (55% relative)

65.3 wet bulb (60% relative)

1750

2000

2250

1750

2000

2250

1750

2000

2250

80

TC

23.0

24.4

25.6

24.7

26.2

27.4

26.3

27.7

29.0

SHC

5.3

6.1

6.8

3.2

4.0

4.7

1.4

2.2

2.9

kW

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

75

TC

23.3

24.6

25.7

25.0

26.3

27.5

26.4

27.8

29.0

SHC

5.1

5.8

6.5

3.1

3.9

4.5

1.4

2.2

2.8

kW

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

2.9

70

TC

23.5

24.8

25.9

25.2

26.4

27.5

26.6

27.9

29.0

SHC

4.8

5.5

6.2

3.0

3.7

4.3

1.4

2.1

2.8

kW

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

60

TC

24.1

25.2

26.1

25.6

26.7

27.7

26.9

28.0

29.0

SHC

4.3

5.0

5.5

2.8

3.4

3.9

1.4

2.0

2.6

kW

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

50

TC

24.7

25.6

26.4

26.1

27.0

27.8

27.2

28.2

29.0

SHC

3.8

4.4

4.8

2.5

3.1

3.5

1.4

2.0

2.4

kW

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

40

TC

25.3

26.0

26.7

26.5

27.3

27.9

27.6

28.3

29.0

SHC

3.3

3.8

4.2

2.3

2.8

3.1

1.4

1.9

2.3

kW

3.1

3.1

3.1

3.2

3.2

3.2

3.2

3.2

3.2

LEGEND
Edb
--- Entering Dry---Bulb
Ewb --- Entering Wet---Bulb
kW

--- Compressor Motor Power Input

Idb

--- Leaving Dry---Bulb

Iwb --- Leaving Wet---Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC

--- Total Capacity (1000 Btuh) Gross

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet---bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

Where: h

ewb

= Enthalpy of air entering evaporator coil

580J