Bryant LEGACY LINE 580J User Manual

Page 36

Advertising
background image

36

Table 20 – COOLING CAPACITIES

1--STAGE COOLING

6 TONS

580J07 (6 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

Air Entering Evaporator --- CFM

Temp (F) Air Ent

Condenser (Edb)

80 dry bulb

80 dry bulb

80 dry bulb

72 wet bulb

67 wet bulb

62 wet bulb

2100

2400

2700

2100

2400

2700

2100

2400

2700

75

TC

86.7

89.9

92.8

79.3

82.3

84.9

71.9

74.6

77.0

SHC

40.1

41.8

43.3

46.9

48.5

49.9

53.7

55.2

56.5

kW

4.3

4.3

4.3

4.2

4.2

4.2

4.2

4.2

4.2

85

TC

79.5

82.6

85.4

72.5

75.3

77.9

65.4

68.0

70.3

SHC

32.1

34.0

35.7

40.7

42.5

44.1

49.4

51.0

52.5

kW

5.0

5.0

5.0

5.0

5.0

5.0

4.9

4.9

4.9

95

TC

72.4

75.3

78.1

65.6

68.3

70.8

58.8

61.3

63.6

SHC

24.1

26.3

28.1

34.6

36.6

38.3

45.1

46.9

48.5

kW

5.8

5.8

5.8

5.7

5.7

5.7

5.6

5.6

5.6

105

TC

65.2

68.1

70.7

58.7

61.4

63.8

52.3

54.7

56.8

SHC

16.2

18.5

20.5

28.5

30.6

32.6

40.7

42.8

44.6

kW

6.5

6.5

6.5

6.4

6.4

6.4

6.3

6.3

6.3

115

TC

58.0

60.8

63.3

51.9

54.4

56.7

45.7

48.0

50.1

SHC

8.2

10.7

13.0

22.3

24.7

26.8

36.4

38.6

40.6

kW

7.2

7.2

7.2

7.1

7.1

7.1

7.0

7.0

7.0

580J07 (6 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

Air Entering Evaporator --- CFM

Temp (F) Air Ent

Condenser (Edb)

75 dry bulb

75 dry bulb

75 dry bulb

62.5 wet bulb (50% relative)

64 wet bulb (55% relative)

65.3 wet bulb (60% relative)

2100

2400

2700

2100

2400

2700

1750

2000

2700

80

TC

16.7

19.8

22.5

18.8

21.9

24.7

16.2

19.4

26.7

SHC

0.6

0.6

0.6

---0.4

---0.4

---0.4

---1.3

---1.3

---1.3

kW

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

75

TC

17.7

20.6

23.1

19.6

22.6

25.3

17.3

20.3

27.1

SHC

0.6

0.6

0.6

---0.3

---0.3

---0.3

---1.2

---1.2

---1.2

kW

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

70

TC

18.6

21.3

23.7

20.5

23.3

25.8

18.3

21.1

27.6

SHC

0.7

0.7

0.7

---0.2

---0.2

---0.2

---1.0

---1.0

---1.0

kW

4.0

4.0

4.0

4.1

4.1

4.1

4.1

4.1

4.1

60

TC

20.5

22.9

25.0

22.2

24.7

26.8

20.4

22.8

28.5

SHC

0.7

0.7

0.7

---0.0

---0.0

---0.0

---0.7

---0.7

---0.7

kW

4.1

4.1

4.1

4.1

4.1

4.1

4.1

4.1

4.1

50

TC

22.4

24.4

26.2

24.0

26.0

27.9

22.4

24.5

29.3

SHC

0.8

0.8

0.8

0.1

0.1

0.1

---0.4

---0.4

---0.4

kW

4.1

4.1

4.1

4.1

4.1

4.1

4.2

4.2

4.2

40

TC

24.3

25.9

27.4

25.7

27.4

28.9

24.5

26.3

30.2

SHC

0.8

0.8

0.8

0.3

0.3

0.3

---0.1

---0.1

---0.1

kW

4.1

4.1

4.1

4.2

4.2

4.2

4.2

4.2

4.2

LEGEND
Edb
--- Entering Dry---Bulb
Ewb --- Entering Wet---Bulb
kW

--- Compressor Motor Power Input

Idb

--- Leaving Dry---Bulb

Iwb --- Leaving Wet---Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC

--- Total Capacity (1000 Btuh) Gross

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

t

lwb

= Wet---bulb temperature corresponding to enthalpy of air

leaving evaporator coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

Where: h

ewb

= Enthalpy of air entering evaporator coil

580J