Burnham CHG225 User Manual
Page 16
 
16
2) This appliance requires a Special Gas Vent. The product is designed to use Burnham supplied AL 29-4C
®
Stainless
Steel vent system components when utilizing the supplied vent adaptor. The following manufacturers offer similar
AL 29-4C
®
components and are approved for use with this product. The use of these alternate manufacturer’s
venting systems can be utilized by connecting directly to the installed vent pipe (supplied adaptor is not required).
See Table 6.5 for complete list of Burnham Vent System Components.
3) Install	Vent	Pipe,	Burnham	Gasketed	Vent	System.
	
Procedure	for	Joining	Burnham	Gasketed	Vent	Pipe	and	Fittings.		See	Fig.	6.7.
a)	 	Wipe	the	male	end	of	each	joint	using	an	alcohol	pad	to	remove	any	dirt	and	grease.
b)	 	Align	weld	seams	in	pipes	and	use	a	slight	twisting	motion	to	FULLY	insert	male	end	into	female	end	of		
joint. Ensure bead in male end of pipe is below locking band and rest against the end of the female pipe. Verify
the factory-installed gasket is not dislodged or cut.
c) Tighten locking band by HAND with a 5/16” nut driver until snug plus ¼ turn. DO NOT SECURE
JOINTS WITH SHEET METAL SCREWS OR POP RIVETS. DO NOT PUNCTURE THE VENT
 SYSTEM!
d)	 	Once	the	installation	is	complete,	operate	appliance	and	inspect	all	joints	to	ensure	that	flue	gases	and/or		
liquid condensate will not escape.
Figure 6.: Burnham Gasketed Vent Joint Detail
4) Assembly	of	Flex-L-Intl.	Star-34	Vent	System:
	
a) Star-34 General Notes:
•	 Do	not	cut	Star-34	vent	components.
•	 Support	horizontal	piping	sections	at	intervals	of	48”	or	less.
•	 Vertical	venting	systems	must	be	supported	by	at	least	one	Star-34	Fire	stop.	An	additional	vertical		
support is required after any offset.
• Orient Star-34 components so that the arrows on the piping labels are in the direction of flue gas flow.
b) Start assembly of the vent system at the boiler. Remove the hose clamp shipped on the CHG vent collar.
Bend the three hose clamp tabs on this collar outward slightly.
c) Clean the exterior of the male end of the first piece of pipe and the inside of the vent collar on the boiler.
Use a cleaner such as Methyl Ethyl Keytone (MEK) or naptha.
d) On the male end of the pipe, apply a ¼” wide bead of silicone approximately ¼” from the end of the pipe
and another ¼” bead against the joint side of the stop bead (Fig 6.7a).
e)	 	Insert	the	male	end	of	the	pipe	into	the	boiler	vent	collar	until	it	bottoms	out.
f)	 	Apply	an	additional	bead	of	silicone	over	the	outside	of	the	joint	and	smooth	out.	
g)	 	Replace	and	tighten	the	clamp	on	the	vent	collar.
h)	 	Clean	the	female	end	of	the	first	piece	of	pipe.	Also	clean	the	male	end	of	the	next	piece	of	pipe.	
i)	 	Apply	silicone	as	in	step	(d)	(Fig	6.7b).
j)	 	Align	the	longitudinal	seams	of	the	pipe	and	insert	the	male	end	of	the	second	pipe	into	the	female	end	of		 	
the first pipe.
k) Insert a Star-34 joiner band into the inlet of the beaded channel. Feed the joiner band in so that it makes its
way around the channel and overlaps by approximately ½” (Fig 6.7b).