12)		Test	any	external	limits	or	other	controls	in	accordance	with	the	manufacturer’s	instructions.
13)		Verify	that	the	boiler	starts	and	stops	in	response	to	calls	for	heat	from	the	heating	thermostat	and	indirect	
water heater thermostat. Make sure that the appropriate circulators also start and stop in response to the
thermostats.
14) As shipped, the heating and indirect water heater set point supply temperatures are both set to 180°F. If
necessary, adjust these to the appropriate settings for the type of system to which this boiler is connected. See
the Operation Section of this manual for information on how to do this.
15) Adjust the heating and indirect water heater thermostats to their final set points.