Method 1: Primary/Secondary Piping - Boiler in Secondary Loop
This method can be used in heat-only applications as shown in Figure 8.2 or with an indirect water heater as
shown in Figure 8.3. This method relies on primary/secondary pumping to ensure that the required flow is always
maintained through the boiler. In this system, the flow rate through the boiler is completely independent of the flow
rate through the heating system. Use the following guidelines to ensure that boiler will have the required flow shown
in Table 8.1 regardless of the flow in the heating system.
1)
Primary Loop Piping - Size the primary circulator and piping to obtain the design flow rate through the heating
system as you would on any other heating system. All piping between the expansion tank and secondary connection
tees must be at least as large as that shown in Table 8.5, column a. In order to keep the flow rates in the primary
and secondary loops independent of each other, provide at least 8 diameters of straight pipe upstream of the first
secondary tee and 4 diameters downstream of the second secondary tee. Keep the distance between the expansion
tank and the first secondary tee as short as practical.
2) Secondary Loop (“Boiler Loop”) Piping – All piping must be the size shown for the boiler in Table 8.5, column a.
To	size	the	circulator:
a)	 	Count	all	fittings	in	the	planned	secondary	loop	(the	secondary	loop	consists	of	the	shaded	piping	in	Figure		 	
8.4a). In doing so, do not count the secondary connection tees, unions, or the fittings supplied with the boiler
(these have already been accounted for).
b) Using Table 8.7, find the equivalent lengths of all fittings in the secondary loop. Total these equivalent lengths
and add them to the total length of planned straight pipe in the secondary loop. The result is the total equivalent
length of the secondary loop.
c) Using Table 8.5, find the boiler size being installed and select a boiler secondary circulator that shows a
“maximum equivalent length” (column d) in excess of the total equivalent length calculated in Step b.
3)
Indirect Water Heater Loop Piping (If Indirect Water Heater is Used) – All piping must be the size shown in Table
8.6, column (a). If the indirect water heater connections are smaller than the pipe size called for in column (a),
reduce	the	pipe	size	at	the	indirect	water	heater	connections.	To	size	the	circulator:
a)	 Count	all	fittings	in	the	planned	Indirect	Water	Heater	Loop	(the	indirect	water	heater	loop	consists	of	the		 	
shaded piping in Figure 8.4b). In doing so, you will be counting some piping and fittings which are common to
the heating system secondary (“boiler loop”) piping and which were counted in Step 2a above. Do not count the
elbows or fittings supplied with the boiler.
b) Using Table 8.7, find the equivalent lengths of all fittings in the indirect water heater loop. Total these equivalent
lengths and add them to the total length of planned straight pipe in the indirect water heater loop.
	 The	result	is	the	total	equivalent	length	of	the	indirect	water	heater	loop.
c)	 	Using	Table	8.6,	find	the	boiler	size	being	installed	and	select	an	indirect	water	heater	loop	circulator	that	shows		
a “maximum equivalent length” (column f) in excess of the total equivalent length calculated in Step b.
Example – Assume that a CHG150 is to be installed in a heating system along with a AL40A indirect water heater. A
total of 15 ft of straight pipe will be installed between the boiler and the primary loop. A total of 20 ft of straight pipe
will be installed between the boiler and the indirect water heater. Fittings are arranged as shown in Figure 8.3. The
AL40A requires a flow rate of 8 GPM and has a head loss of 3.0 ft.
Total	fittings	in	Secondary	loop	(“boiler	loop”):
	 7	90	Elbows	
2 Runs of Tees
1 Swing Check
2 Isolation Valves
Note: Unions, Secondary Connection Tees, and factory supplied fittings are ignored.
Calculate	total	equivalent	length	from	Table	8.7:
	 15ft	Straight	Pipe	+	7	Elbows	x	3.75	+	2	Runs	of	Tees	x	2.5	+	1	Swing	Check	x	10	+	2	valves	x	0.8	=	57.85		 	
Equivalent Feet Straight Pipe. From Table 8.5, we see that a Taco 007 will pump 8 GPM through a CHG150
with 148 equivalent feet of pipe, so Taco 007 is OK.
Total	fittings	in	Indirect	Water	Heater	Loop:
	 6	90	Elbows	
1 Swing Check
2 Turns in Tees
2 Isolation Valves
Calculate total equivalent length from Table 8.7:
20 Straight Pipe + 6 Elbows x 3.75 + 2 Turns in Tees x 8 + 1 Swing Check x 10 + 2 valves x 0.8 = 70.1
Equivalent Feet Straight Pipe. From Table 8.6, we see that smallest circulator which will pump at 8 GPM
through a CHG150 with 70.1 equivalent feet and an indirect water heater pressure drop of 3 ft is a Taco 0010.