Figure 10.2: Gas Valve Detail

11) Perform a combustion test. On horizontally vented units, the sample probe may be inserted into the terminal.

If this is not possible, and if no sample tap is present in the vent system, remove the flue temperature sensor

and insert the analyzer probe in the sensor opening. On the CHG150 and CHG225 the flue temperature probe

is located behind the lower vestibule door. For the boiler to operate, this sensor will need to be temporarily

connected outside of the boiler. If it is removed, be sure to return the flue gas temperature sensor to its original

position after combustion testing is complete.

Check CO2 (or O2) and CO at both high and low fire. The boiler may be temporarily locked into high or low

fire for 15 minutes as follows:
a) To lock the boiler in high fire, simultaneously press and hold the “Mode” button and “+“ button until

the display flashes “H”, indicating that the boiler has been driven to high fire. After this happens, allow the

boiler to operate for approximately 5 minutes before taking combustion readings.

b) To lock the boiler in low fire, simultaneously press and hold the “Mode” button and “-“ button until

the display flashes “L”, indicating that the boiler has been driven to low fire. After this happens, allow

the boiler to operate for approximately 5 minutes before taking combustion readings.

At both high and low fire, CO readings should be less than 75 PPM. Typical CO2 readings are shown in Table

10.3.

Normal modulation of the boiler should return 15 minutes after the boiler is locked in high or low fire.

Table 10.3: Typical CO2/O2 Combustion readings range

Model

Fuel

%CO2

%O2

CHG150 Natural Gas

8.2

6.3

CHG225 Natural Gas

8.7

5.4

CHG150

Propane

NA

NA

CHG225

Propane

10.2

5.4

warNINg

EaCh Chg sErIEs bOIlEr Is TEsTED aT ThE faCTOry aND aDJusTmENTs

To THE AIR-FuEL MIxTuRE ARE NoRMALLy NoT NECESSARy. CoNSuLT A

BuRNHAM REPRESENTATIVE BEFoRE ATTEMPTING To MAkE ANy SuCH

aDJusTmENTs. ImPrOPEr gas ValVE Or mIxTurE aDJusTmENTs COulD

RESuLT IN PRoPERTy DAMAGE, PERSoNAL INjuRy, oR LoSS oF LIFE.