Burnham CHG225 User Manual
Page 17
 
17
Figure 6.7b: Star-34 Connections
l)	 	Cut	the	excess	joiner	band	so	that	it	lays	flat	in	the	beaded	channel	(Fig	6.7b).	
m)		Fill	the	inlet	of	the	beaded	channel	with	silicone.	Smooth	the	silicone	over	the	channel	inlet	as	well	as	the		 	
silicone between the female end and the stop bead of the male end (Fig 6.7b).
n)	 	Repeat	Steps	(h)	–	(m)	for	the	remaining	Star-34	components.	
p)	 	Allow	the	silicone	to	cure	per	the	silicone	manufacturer’s	instructions	before	operating	the	boiler.		 	
5) Assembly of Z-Flex Z-Vent III:
a) General Notes:
• Non-expanded ends of SVE Series III piping sections may be cut using aviation snips or a 24 thread per inch
hacksaw. File or sand the cut end smooth before assembling. See the following instructions.
•	 Support	horizontal	piping	sections	at	intervals	of	48”	or	less.
•	 Vertical	venting	systems	must	be	supported	by	at	least	one	Z-Flex	fire	stop.	An	additional	vertical		
support is required after any offset and as required by the Z-Vent III installation instructions.
b) Start assembly of the vent system at the boiler. Remove the hose clamp shipped on the CHG vent collar.
Bend the three hose clamp tabs on this collar outward slightly.
c) Clean the exterior of the male end of the first piece of pipe and the inside of the vent collar on the boiler.
Remove dirt, grease, and moisture from the surfaces to be sealed. Dry surfaces or allow to dry thoroughly.
d) On the male end of the pipe, apply a ¼” wide bead of high temperature silicone approximately ½ inch from the
male end of the pipe. Apply ¼” beads of silicone along both sides of the longitudinal seam (Fig. 6.8).
e)	 	Insert	the	male	end	of	the	pipe	into	the	boiler	vent	collar	until	it	bottoms	out.
f)	 Apply	an	additional	bead	of	silicone	over	the	outside	of	the	joint	and	smooth	out.	
g)	 Replace	and	tighten	the	clamp	on	the	vent	collar.
h)	 The	female	end	of	each	Z-Vent	III	component	has	a	silicone	sealing	gasket.	Examine	all	vent	components		 	
to insure that the gasket integrity has remained during shipping. Gaskets must be in the proper position or
flue gas could leak resulting in carbon monoxide poisoning.
Figure 6.7a: Star-34 Connection to Vent Collar