Iii before installing, Iv locating the boiler – Burnham CHG225 User Manual
Page 4
 
4
III Before Installing
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict
accordance	with	this	manual	and	the	authority	having	jurisdiction.	
•	 In	the	absence	of		an	authority	having	jurisdiction,	installation	must	be	in	accordance	with	this	manual	and		
the National Fuel Gas Code, ANSI Z223.1.
• Where required by the authority having jurisdiction, this installation must conform to the Standard for
Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).
2) CHG boilers utilize aluminum heat exchangers constructed, tested, and stamped in accordance with ASME
Boiler and Pressure Vessel Code Case 2382-2. Some jurisdictions which require ASME boiler construction
do not recognize this Code Case and may not approve the installation of an aluminum boiler. Consult the
authority having jurisdiction before installing this boiler.
3) Read Section VI to verify that the maximum combustion air and exhaust pipe lengths will not be exceeded in
the planned installation. Also verify that the vent terminal is installed in the proper location.
4) Make sure that the boiler is correctly sized:
• For heating systems employing convection radiation (baseboard or radiators), use an industry accepted
sizing method such as the I=B=R Heat Loss Calculation Guide (Pub. #H21 or #H22) published by the
Hydronics Institute in Berkeley Heights, NJ.
•	 For	new	radiant	heating	systems,	refer	to	the	radiant	tubing	manufacturer’s	boiler	sizing	guidelines.	
•	 For	systems	including	an	Alliance™	indirect	water	heater,	size	the	boiler	to	have	either	the	DOE	Heating	
Capacity required for the Alliance™ or the net rating required for the heating system, whichever results in
the larger boiler.
• For systems that incorporate other indirect water heaters, refer to the indirect water heater manufacturer’s
instructions for boiler output requirements.
5)	 Make	sure	that	the	boiler	received	is	configured	for	the	correct	gas	(natural	or	LP).
6)	 Make	sure	that	the	boiler	is	configured	for	use	at	the	altitude	at	which	it	is	to	be	installed.	
IV Locating the Boiler
1) Observe the minimum clearances shown in Figure 4.1. These clearances apply to both combustible and non-
combustible materials. Observe the minimum clearances to combustibles for vent pipe shown in Table 4.2.
2) Note the recommended service clearances in Figure 4.1. The recommended service clearances may be
reduced to the minimum combustible clearances with the understanding that servicing the boiler will become
increasingly difficult as the clearance is reduced.
3)	 Boiler	may	be	installed	on	non-carpeted	combustible	surface.
4)	 The	relief	valve	must	be	installed	in	the	factory	specified	location.
5)	 The	boiler	should	be	located	so	as	to	minimize	the	length	of	the	vent	system.
6)	 The	combustion	air	piping	must	terminate	where	outdoor	air	is	available	for	combustion	and	away	from	areas	
that will contaminate combustion air. Avoid areas near chemical products containing chlorine, chloride based
salts, chloro/fluorocarbons, paint removers, cleaning solvents and detergents.
NOTICE
ThIs PrODuCT musT bE INsTallED by a lICENsED PlumbEr Or gas fITTEr
whEN INsTallED wIThIN ThE COmmONwEalTh Of massaChusETTs. sEE
aPPENDIx a fOr aDDITIONal ImPOrTaNT INfOrmaTION abOuT INsTallINg
ThIs PrODuCT wIThIN ThE COmmONwEalTh Of massaChusETTs.