xIV Troubleshooting

A. Troubleshooting problems where no error code is displayed:

CONDITION

POSSIBLE CAUSES

Display Blank, Fan off, LWCO lights off

• No 120VAC Power at boiler. Check breaker and wiring

between breaker panel and boiler

Display Panel Blank, Fan running

• Loose 120VAC connection wiring between boiler J-Box and

MCBA

• Blown “F1” fuse in MCBA (see Figure 13.2 for location).

Replace with 5A fuse provided

Display reads “U.125” continuously, Fan running

• Defective AT250 transformer

• Blown “F3” fuse in MCBA (see Figure 13.2 for location).

Replace with 4A slow-blow fuse provided

Boiler not responding to call for heat, Status code on display

=”0” (see Figure 11.1)

• Boiler is not seeing call for heat. Check thermostat or

zone wiring for loose connection, miswiring, or defective

thermostat/zone control.

Boiler fires, but display panel is blank

• Loose ribbon cable

• Defective display

warNINg

TuRN oFF PoWER To BoILER BEFoRE REPLACING FuSES oR WoRkING oN

wIrINg.

Table 13.1: No Error Code Displayed

Figure 13.2: MBCa Fuse Location