602A CORNER WEIGHTS (IN POUNDS)

SELECTION PROCEDURE (WITH EXAMPLE)

I Determine cooling and heating requirements at design

conditions:

Given:
Required Cooling Capacity (TC) . . . . . . . . . . .28,000 Btuh
Sensible Heat Capacity (SHC). . . . . . . . . . . . .20,500 Btuh
Required Heating Capacity . . . . . . . . . . . . . . .28,550 Btuh
Outdoor Entering Air Temperature. . . . . . . . . . . . . . . 95°F
Outdoor-Air Winter Design Temperature . . . . . . . . . . 20°F
Indoor-Air Winter Design Temperature . . . . . . . . . . . 70°F
Indoor Entering-Air Temperature . . . . . . . . . . . . . 80°F edb

67°F ewb

Indoor-Air Quantity. . . . . . . . . . . . . . . . . . . . . . . . 1125 cfm
External Static Pressure . . . . . . . . . . . . . . . . . .0.20 in. wg
Electrical Characteristics (V-Ph-Hz). . . . . . . . . . . 230-1-60
edb — entering dry bulb
ewb — entering wet bulb

II Select unit based on required cooling capacity.

Enter Cooling Extended Performance table at outdoor
entering-air temperature of 95°F, indoor air entering at 1125
cfm and 67°F ewb (entering wet bulb). The 030 unit will
provide a total cooling capacity of 30,900 Btuh and a
sensible heat capacity of 24,800 Btuh.
For indoor-air temperature other than 80°F edb (entering dry
bulb), calculate sensible heat capacity correction, as
required, using the formula found in Note 3 following the
cooling capacities tables. NOTE: Unit ratings are net
capacities.

III Select electric heat.

Enter the 030 units Heating Extended Performance table at
1125 cfm. At 70°F return indoor air and 20°F air entering
outdoor coil, the integrated heating capacity is 16,200 Btuh.
(Select integrated heating capacity value since deductions
for outdoor-coil frost and defrosting have already been
made. No correction is required.)
The required heating capacity is 28,550 Btuh. Therefore,
12,350 Btuh (28,550 – 16,200) additional electric heat is
required.
Determine additional electric heat capacity in kW.
12,350 Btuh
3414 Btuh/kW

Enter the Electric Heater table on page 5 for 208/230 v,
single-phase, unit. The 5-kW heater at 240 v most closely
satisfies the heating required. To calculate kW at 230 v,
multiply the heater kW by multiplication factor 0.92 found in
the Multiplication Factors table on page 17.
5 kW x 0.92 = 4.6 kW
4.6 kW x 3414 = 15,704 Btuh
Total unit heating capacity is 31,900 Btuh (16,200 + 15,704).

IV

Determine fan speed and power requirements at design
conditions.
Before entering the air delivery tables, calculate the total
static pressure required.

–

CORNER WEIGHTS (Small Cabinet)

CORNER WEIGHTS (Large Cabinet)

Unit

24

30

36

—

—

Unit

42

48

60

Total Weight (lbs.)

299

320

328

—

—

Total Weight (lbs.)

350

375

428

Corner Weight 1

63

63

64

—

—

Corner Weight 1

75

81

92

Corner Weight 2

62

74

76

—

—

Corner Weight 2

49

52

60

Corner Weight 3

56

56

58

—

—

Corner Weight 3

95

102

116

Corner Weight 4

118

127

130

—

—

Corner Weight 4

131

140

160

1

2

4

3

x

y

= 3.6 kW of heat required

Model 602A