Performance data (cont) – Bryant 602A User Manual

Page 12

Advertising
background image

—12—

PERFORMANCE DATA (cont)

COOLING EXTENDED PERFORMANCE TABLE

HEATING EXTENDED PERFORMANCE TABLE

-10–20

HEATING EXTENDED PERFORMANCE TABLE 30–60

*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.

602A030 (2.5 TONS)

Temp (F)

Air Ent

Outdoor Coil

(Edb)

Indoor Entering Air—CFM/BF

875/0.05

1000/0.06

1125/0.08

Indoor Entering Air—Ewb (F)

72

67

63*

62

72

67

63*

62

72

67

63*

62

85

TC

34.1

31.8

29.1

28.7

34.4

32.0

29.6

29.0

34.3

32.0

30.1

29.6

SHC

17.8

22.9

21.6

26.8

18.3

24.2

23.1

28.1

18.7

24.0

24.4

29.6

kW

2.36

2.37

2.39

2.36

2.45

2.47

2.50

2.44

2.57

2.59

2.59

2.54

95

TC

33.2

30.1

27.9

27.5

33.4

29.5

28.1

27.9

33.5

30.9

28.2

27.8

SHC

17.5

22.0

21.1

26.4

18.1

22.8

22.3

27.5

18.5

24.8

23.2

27.8

kW

2.67

2.69

2.68

2.64

2.76

2.78

2.79

2.72

2.88

2.89

2.90

2.82

105

TC

31.9

28.7

26.5

26.2

32.4

29.1

26.6

26.4

32.1

29.6

26.8

27.1

SHC

17.0

21.44

20.6

25.7

18.1

22.9

21.7

26.4

18.2

24.4

22.7

27.1

kW

3.01

3.02

3.00

2.95

3.07

3.12

3.09

3.03

3.23

3.21

3.20

3.13

115

TC

30.5

27.0

24.9

24.4

30.6

27.2

25.1

25.5

30.6

27.3

25.1

25.9

SHC

16.7

20.8

19.9

24.4

17.2

21.9

21.1

25.5

17.7

23.0

22.0

25.9

kW

3.38

3.36

3.33

3.28

3.48

3.46

3.43

3.37

3.59

3.56

3.55

3.48

602A030 (2.5 TONS)

Temp (F)

Indoor Air Cfm (std)

Air Temperature Entering Outdoor Coil (F db at 70% rh)

Ent Indoor Coil

-10

0

10

17

20

60

875

TC

9.33

8.58

11.76

10.82

12.89

11.86

16.26

14.96

17.29

15.91

kW

1.75

1.82

1.70

1.92

1.94

1000

TC

9.69

8.92

12.27

11.29

15.02

13.82

16.62

15.29

17.78

16.36

kW

1.82

1.87

1.90

1.98

2.02

1125

TC

10.11

9.31

12.74

11.72

15.47

14.23

17.13

15.76

18.11

16.66

kW

1.99

1.95

1.99

2.05

2.05

70

875

TC

6.14

5.65

11.04

10.16

13.93

12.81

16.58

15.26

16.72

15.38

kW

1.99

1.97

2.01

2.48

2.09

1000

TC

8.82

8.11

11.58

10.66

14.36

13.21

16.38

15.06

17.13

15.75

kW

1.96

2.03

2.09

2.13

2.16

1125

TC

9.32

8.58

11.94

10.99

14.84

13.66

16.85

15.51

17.61

16.20

kW

2.06

2.08

2.18

2.22

2.24

80

875

TC

7.35

6.76

10.12

9.31

12.67

11.66

15.23

14.01

16.17

14.88

kW

2.04

2.16

2.22

2.28

2.30

1000

TC

7.74

7.13

10.71

9.86

13.44

12.37

15.71

14.46

16.68

15.35

kW

2.13

2.23

2.19

2.33

2.34

1125

TC

8.22

7.56

11.07

10.18

14.06

12.94

16.24

14.94

17.20

15.83

kW

2.24

2.32

2.39

2.42

2.43

602A030 (2.5 TONS)

Temp (F)

Indoor Air Cfm (std)

Air Temperature Entering Outdoor Coil (F db at 70% rh)

Ent Indoor Coil

30

40

47

50

60

60

875

TC

20.22

18.60

25.04

25.04

28.62

28.62

29.88

29.88

34.18

34.18

kW

1.95

1.86

2.07

2.08

2.13

1000

TC

20.67

19.02

26.18

26.18

28.82

28.82

30.02

30.02

34.84

34.84

kW

1.98

2.04

2.07

2.09

2.12

1125

TC

21.16

19.47

26.52

26.52

29.60

29.60

30.04

30.04

34.89

34.89

kW

2.06

2.11

2.06

2.13

2.14

70

875

TC

19.95

18.35

25.29

25.29

28.10

18.68

29.32

29.31

33.61

33.61

kW

2.23

2.25

2.30

2.34

2.40

1000

TC

20.16

18.55

25.80

25.79

28.37

28.37

29.57

29.57

33.62

33.62

kW

2.23

2.29

2.32

2.34

2.38

1125

TC

20.55

18.91

26.12

26.12

28.59

28.59

29,70

29.70

33.74

33.74

kW

2.31

2.34

2.37

2.39

2.40

80

875

TC

19.18

17.65

24.91

24.91

27.49

27.49

28.74

28.74

33.00

33.00

kW

2.40

2.52

2.59

2.60

2.68

1000

TC

19.46

17.91

25.31

25.31

27.93

27.93

29.09

29.09

33.18

33.18

kW

2.46

2.54

2.61

2.61

2.67

1125

TC

19.93

18.34

25.73

25.73

28.25

28.25

29.41

29.41

33.15

33.15

kW

2.52

2.61

2.63

2.66

2.70

Advertising