PERFORMANCE DATA (cont)

COOLING EXTENDED PERFORMANCE TABLE

HEATING EXTENDED PERFORMANCE TABLE

-10–20

HEATING EXTENDED PERFORMANCE TABLE 30–60

*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.

602A036 (3 TONS)

Temp (F)

Air Ent

Outdoor Coil

(Edb)

Indoor Entering Air—CFM/BF

1050/0.11

1200/0.14

1350/0.18

Indoor Entering Air—Ewb (F)

72

67

63*

62

72

67

63*

62

72

67

63*

62

85

TC

37.4

35.2

33.4

32.3

37.8

35.8

34.2

33.7

38.5

36.2

34.6

34.2

SHC

19.1

25.1

25.0

30.3

19.9

26.7

26.7

32.7

20.9

28.0

28.1

34.2

kW

3.18

3.15

3.13

3.12

3.19

3.16

3.14

3.13

3.20

3.17

3.14

3.14

95

TC

37.1

34.7

30.4

29.2

37.6

35.2

32.6

31.7

38.0

35.7

33.1

32.4

SHC

19.2

25.4

22.5

27.5

20.2

27.1

26.0

30.5

21.1

28.7

27.7

32.4

kW

3.48

3.44

3.33

3.30

3.49

3.45

3.41

3.38

3.40

3.46

3.42

3.39

105

TC

36.2

32.5

28.0

27.7

36.8

33.7

29.7

28.5

37.1

34.1

31.3

31.2

SHC

19.0

24.1

20.9

26.5

20.1

26.5

23.0

28.5

21.1

28.3

26.7

31.2

kW

3.78

3.69

3.54

3.54

3.80

3.74

3.61

3.56

3.80

3.76

3.66

3.62

115

TC

34.7

29.5

26.6

27.2

35.4

31.5

27.5

26.6

35.8

32.1

28.2

27.5

SHC

18.6

22.0

20.4

26.3

19.9

25.4

22.4

26.6

20.9

27.3

24.5

27.5

kW

4.09

3.89

3.81

3.78

4.11

3.98

3.82

3.80

4.11

4.00

3.85

3.83

602A036 (3 TONS)

Temp (F)

Indoor Air Cfm (std)

Air Temperature Entering Outdoor Coil (F db at 70% rh)

Ent Indoor Coil

-10

0

10

17

20

60

1050

TC

8.92

8.25

11.90

11.01

16.46

15.22

18.09

16.73

18.82

17.40

kW

2.15

2.25

2.36

2.43

2.46

1200

TC

9.67

8.94

15.19

14.05

17.32

16.01

18.88

17.46

19.62

18.15

kW

2.33

2.35

2.49

2.56

2.60

1350

TC

10.23

9.46

15.98

14.78

18.08

16.72

19.64

18.16

20.39

18.85

kW

2.55

2.55

2.65

2.73

2.76

70

1050

TC

6.60

6.11

13.40

12.40

15.70

14.52

17.40

16.09

18.13

16.77

kW

2.25

2.35

2.50

2.59

2.62

1200

TC

8.18

7.57

14.12

13.06

16.69

15.44

18.28

16.90

19.06

17.63

kW

2.46

2.54

2.64

2.72

2.76

1350

TC

9.11

8.43

10.80

9.99

17.50

16.19

19.09

17.65

19.82

18.33

kW

2.46

2.55

2.81

2.89

2.93

80

1050

TC

6.31

5.83

9.72

8.99

14.64

13.54

16.52

15.28

17.34

16.03

kW

2.39

2.51

2.68

2.74

2.77

1200

TC

6.84

6.32

13.07

12.09

15.68

14.50

17.69

16.36

18.34

16.96

kW

2.57

2.69

2.82

2.86

2.91

1350

TC

8.22

7.61

11.65

10.77

16.59

15.34

18.42

17.04

19.19

17.75

kW

2.80

2.89

3.00

3.06

3.09

602A036 (3 TONS)

Temp (F)

Indoor Air Cfm (std)

Air Temperature Entering Outdoor Coil (F db at 70% rh)

Ent Indoor Coil

30

40

47

50

60

60

1050

TC

20.96

29.39

31.09

31.09

33.90

33.90

35.17

35.17

39.37

39.37

kW

2.60

2.55

2.66

2.73

2.92

1200

TC

21.86

20.22

31.69

31.69

34.41

34.41

35.57

35.57

39.77

39.77

kW

2.72

2.61

2.72

2.77

2.93

1350

TC

22.69

20.98

32.29

32.29

34.81

34.81

35.93

35.93

40.18

40.18

kW

2.88

2.74

2.85

2.88

2.97

70

1050

TC

20.12

18.61

30.63

30.63

33.55

33.55

34.81

34.81

39.17

39.17

kW

2.74

2.71

2.87

2.93

3.14

1200

TC

21.06

19.47

31.35

31.35

34.20

34.20

35.47

35.47

39.37

39.37

kW

2.88

2.90

2.93

3.00

3.16

1350

TC

21.91

20.27

32.10

32.10

34.77

34.77

35.80

35.80

39.55

39.55

kW

3.06

2.96

3.07

3.13

3.26

80

1050

TC

19.93

18.43

29.99

29.99

33.00

33.00

34.36

34.36

38.68

38.68

kW

2.94

2.91

3.06

3.14

3.39

1200

TC

20.22

18.70

31.26

31.26

33.87

33.87

35.11

35.11

39.22

39.22

kW

3.04

3.10

3.16

3.22

3.41

1350

TC

21.11

19.52

31.80

31.80

34.60

34.60

35.79

35.79

39.46

39.46

kW

3.22

3.16

3.29

3.34

3.54

Advertising