Electric heaters, Options and accessories – Bryant 602A User Manual

Page 5

Advertising
background image

—5—

Factory-installed options
Louvered grille

provides hail and vandalism protection. A wire

grille is standard on all models. See model number
nomenclature for louvered grille options.

Coil options

include copper/copper and vinyl-coated

construction for refrigerant coils. Units are shipped standard with
copper tube/aluminum fin construction. See model number
nomenclature for coil options.

Field-installed accessories

Economizer with solid-state controls and barometric relief
dampers

includes filter racks and provide outdoor air during

cooling and reduce compressor operation.

Manual outside air damper

includes hood and filter rack with

adjustable damper blade for up to 25% outdoor air.

Electric heaters

provide heat in the unit when required. Each

package has a heater module that slides into the controls
compartment. Heater sizes range from 5.0 to 20.0 kW. The
electric heater design allows the use of a single-point power
supply for the entire unit, resulting in lower installed costs.

Flat roof curbs

in both 8 in. and 14 in. sizes are available for roof

mounted applications.

Square-to-round duct transition kit

enables 024-048 size

units to be fitted to 14 in. round ductwork.

Thermostats

provide control for the system heating and cooling

functions. Thermostat models are available in both programmable
and non-programmable versions.

Controls upgrade kit

supplies high and low pressure safety

protection and protects the unit from operating in unsuitable
conditions.

Crankcase heater

provides anti-floodback protection for low-

load cooling applications.

Rigging kit

includes lifting brackets which are inserted into the

unit base rigging holds to rig unit for rooftop applications.

Low-ambient kit (Motormaster II control)

allows the use of

mechanical cooling down to outdoor temperatures as low as 0°F.

Filter rack

features easy installation, serviceability, and high-

filtering performance for vertical and horizontal applications.

Compressor Hard start kit

gives a boost to the compressor

motor at each start-up.

Economizer with Solid-State Controls and Barometric

Relief Dampers

Manual Air Damper (25% open)

Electric Heaters

Filter Rack

Flat Roof Curbs (8-in. and 14-in.)

Square-to-Round Duct Transition Kit

Thermostats

Controls Upgrade Kit

Crankcase Heater

Rigging Kit

Low Ambient Kit (Motormaster® II Control)

Solid-State Time Guard® II Device

Compressor Hard Start Kit

ELECTRIC HEATERS

LEGEND

ODS — Order Distribution System
NOTE: Electric heaters are rated at 240 v and 480 v. Refer to Multiplication Factors table for other voltages.

*The 030 size models must be run on medium or high speed when used in conjunction with 15 Kw electric heat accessory.

ODS CATALOG

ORDERING NO.

NOMINAL CAPACITY

(kW)

USED WITH SIZES

024

030

036

042

048

060

ELECTRIC HEATERS (208/230 — SINGLE PHASE — 60 Hz)

CPHEATER052A00

5.0

X

X

X

X

CPHEATER064A00

5.0

X

X

CPHEATER070A00

7.5

X

X

X

X

X

X

CPHEATER050A00

10.0

X

X

X

X

X

X

CPHEATER066A00

15.0

X

X

X

X

X

CPHEATER054A00

20.0

X

X

X

ELECTRIC HEATERS (208/230 — THREE PHASE — 60 Hz)

CPHEATER055A00

5.0

X

X

X

X

X

CPHEATER056A00

10.0

X

X

X

X

CPHEATER068A00

10.0

X

CPHEATER058A00

15.0

X

X

X

X

X

CPHEATER067A00

20.0

X

X

X

ELECTRIC HEATERS (460 — THREE PHASE — 60 Hz)

CPHEATER060A00

5.0

X

X

X

X

CPHEATER061A00

10.0

X

X

X

X

CPHEATER062A00

15.0

X

X

X

X

CPHEATER063A00

20.0

X

X

X

Minimum Airflow for Reliable Electric Heater Operation

UNIT-602A

024

030

036

042

048

060

AIRFLOW

800

1000*

1200

1400

1600

2000

OPTIONS AND ACCESSORIES