APPLICATION DATA

Condensate trap — A 2-in. condensate trap must be field
supplied.

Ductwork — Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit
with flanges.

To convert a unit to downflow discharge — Units are
equipped with factory-installed inser ts in the down-flow
openings. Remove the inserts similar to removing an electrical
knock-out.

Maximum cooling airflow — To minimize the possibility of
condensate blow-off from the evaporator, airflow through the
units should not exceed 450 cfm/ton.

Minimum cooling airflow — The minimum cooling airflow is
350 cfm/ton.

Minimum cooling ambient operating temperature — All
standard units have a minimum ambient operating temperature of
40°F. With accessory low ambient temperature kit, units can
operate at temperatures down to 0°F.

1” MIN.

2” MIN.

TRAP