2 - 9

IP

N 07

4-

54

4-

P1

B

CI-100 Crucible Indexer Operating Manual

On the CI-100 rear panel, set Select Switch #5 Down. On the SQC-310 System
Menu / Sensors & Sources, set up the Source with:

Number of Positions: 4

Control Type: Individual

Feedback Type: In Position

Indexer Delay: 5 seconds

2.8.2 Interfacing to IC6 Deposition Controller

The INFICON IC6 does not support binary indexer wiring. BCD wiring between the
CI-100 and the IC6 is required.

The cable wiring below interfaces the IC6 I/O Board connectors to the CI-100 BCD
I/O connector:

IC6 Relay

CI-100 BCD I/O

Pin 6 (Relay 1, NO)----->----Pin 1

Pocket Bit1 Select

Pin 8 (Relay 2, NO)----->----Pin 2

Pocket Bit2 Select

Pin 10 (Relay 3, NO)---->----Pin 7

Pocket Bit3 Select

Pin 7,9,11(Relay Common)-Pin 6

Common

IC6 Input

CI-100 BCD I/O

Pin 15 (Input 1)------<--------Pin 5

Pocket Ready B

Pin 1---------------------------- Pin 6

Common

Short Pin 3 to 9

Interlock

Short Pin 4 to 8

Pocket Ready A

On the CI-100 rear panel, set Select On/Off Switch #5 UP and #7 DOWN. Turn the
CI-100 Off, then On, to read the switch change.

On the IC6 Source menu select Number of Crucibles=8, Crucible Output = 1, and
Crucible Output Type =NO. Set Turret Feedback = Yes and Turret Input = 1.