Caution, Condensate drain trap, Condensate drain trap freeze protection – Bryant 4-WAY MULTIPOISE 359AAV User Manual

Page 17

Advertising
background image

17

Condensate Drain Trap

This furnace removes both sensible and latent heat from the

products of combustion. Removal of the latent heat results in

condensation of the water vapor. The condensate is removed from

the furnace through the drains in the plastic transition and the

vent fitting. The drains connect to the externally mounted

condensate drain trap on the left or right side of the furnace.
The start--up of a new furnace will involve a cycle or two of the

furnace to properly prime the condensate trap with water. Until

the trap is fully primed, some condensate will be pulled into the

combustion blower. The furnace may cycle on the pressure switch

connected to the plastic transition box due to condensate buildup.

After the trap is primed, the condensate will start draining from

the furnace. The combustion blower will clear out any remaining

condensate in the blower housing through the vent fitting

downstream of the blower. Note that the condensate trap can also

be primed by pouring water into the

1

/

2

″ drain hose. Remove

the

1

/

2

″ ID drain hose from either the gutter or the white PVC tee

trap. Using a funnel pour eight (8) ounces of water into

1

/

2

″(13

mm) ID drain hose. Water will flow through the drain hose and

into the condensate drain trap. This will prime both the vent and

the transition sides of the trap. Reconnect the

1

/

2

″(13 mm) ID

drain hose to the original component, either the gutter or the PVC

tee trap.
The condensate drain trap supplied with the furnace MUST be

used. The drain connection on the condensate drain trap is sized

for

3

/

4

″ PVC or CPVC pipe, however alternate

1

/

2

″(13 mm)

CPVC (nominal

5

/

8

″ O.D.) or vinyl tubing with a minimum inner

diameter (I.D.) of

5

/

8

″ may also be used, as allowed by local

codes. Alternate drain pipes and hoses may be used as allowed by

local codes.
The drain line must maintain a

1

/

4

″ (6 mm) per foot downward

slope toward the drain.

1

/

4

″ (6 mm) per foot is recommended.

Installation of an overflow line is recommended when the

1

/

4

″ (6

mm) per foot slope to the condensate drain cannot be maintained.

A drain tube clip is included in the furnace to prevent

kinking/buckling of the drain tube. The clip should remain in the

furnace (between the door switch plate and the blower shelf, Fig.

9) during operation. See Fig. 19 for proper routing and

installation of the overflow.
DO NOT trap the drain line in any other location than at the

condensate drain trap supplied with the furnace.

FROZEN AND BURST WATER PIPE HAZARD
Failure to follow this caution may result in property damage.
If a condensate pump is installed, a plugged condensate drain

or a failed pump may cause the furnace to shut down. Do

not leave the home unattended during freezing weather

without turning off water supply and draining water pipes or

otherwise protecting against the risk of frozen pipes.

CAUTION

!

If possible, DO NOT route the drain line where it may freeze.

The drain line must terminate at an inside drain to prevent

freezing of the condensate and possible property damage.

1. A condensate sump pump MUST be used if required by

local codes, or if no indoor floor drain is available. The

condensate pump must be approved for use with acidic

condensate.

2. A plugged condensate drain line or a failed condensate

pump will allow condensate to spill. If the furnace is in-

stalled where a condensate spill could cause damage, it is

recommended that an auxiliary safety switch be installed

to prevent operation of the equipment in the event of pump

failure or plugged drain line. If used, an auxiliary safety

switch should be installed in the R circuit (low voltage)

ONLY.

3. If the auxiliary switch in the condensate pump is used, the

furnace may shut down due to a blocked condensate line

or failed pump. To prevent frozen water pipes see the

“Frozen Water Pipe Hazard” Installation Section of this

manual.

Drain Tube

Clip

Door
Switch

Blower
Shelf

Representative drawing only, some models may vary in appearance.

A07705

Fig. 9 -- Drain Tube Clip Location

Condensate Drain Trap Freeze Protection

Special precautions MUST be made if installing furnace in an

area which may drop below freezing. This can cause improper

operation or damage to the equipment. If the the furnace

environment has the potential of freezing, the drain trap and drain

line must be protected. Use 3 to 6 watt per foot at 115 volt, 40° F

(4° C) self--regulating shielded and waterproof heat tape. Wrap

the drain trap and drain line with the heat tape and secure with the

ties. Follow the heat tape manufacturer’s recommendations.

359AA

V

Advertising